Zones installed, Zones enabled, Zones disabled – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 88: Zones installed zones enabled zones disabled

Advertising
background image

88

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Programming

Master Programming Level

panel. Do not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a
PAS condition. Attempting to do so will generate an error message and will be prevented by
software checks.

Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 98 On and Pre-signal 98 Off. When Zone 98 is
programmed On, a Pre-signal activation of any device will cause Zone 98 to activate. By assigning
Zone 98 to a control module in the Programming Zone Assignment Screen, an output device
connected to the control module can be used to indicate a Pre-signal condition in the control panel.
Do not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-
signal condition. Attempting to do so will generate an error message and will be prevented by
software checks.

Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause
the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to “Two Stage
Operation” on page 98
for a description of this feature.

Zones Installed

Pressing 1 for Zones Installed, while viewing Zone Setup Screen #2, will display a screen similar to
the following:

This display will show all of the zones that have been programmed into the control panel. Note that
an up and/or down arrow may appear in the upper right corner of the display, indicating that
additional screens of zone information exists. Press the up or down arrow keys to view the
additional zones.

Zones Enabled

Pressing 2 for Zones Enabled, while viewing Zone Setup Screen #2, will display a screen similar to
the following:

This display will show all of the zones that are enabled in the control panel. Note that an up and/or
down arrow may appear in the upper right corner of the display, indicating that additional screens
of zone information exists. Press the up or down arrow keys to view the additional zones.

Zones Disabled

Pressing 3 for Zones Disabled, while viewing Zone Setup Screen #2, will display a screen similar
to the following:

This display will show all of the zones that are disabled in the control panel. Note that an up and/or
down arrow may appear in the upper right corner of the display, indicating that additional screens
of zone information exists. Press the up or down arrow keys to view the additional zones.

ZONE SETUP

1=ZONES INSTALLED

2=ZONES ENABLED

3=ZONES DISABLED

Zone Setup Screen #2

ZONES INSTALLED

00 01 02 03 04 05

Zones Installed Screen

ZONES ENABLED

00 01 02 04 05 06 07

08 09 10 11 12 13 14

15 16 17 18 19 20 21

Zones Enabled Screen

ZONES DISABLED

03

Zones Disabled Screen