6 verify loop, 7 history, View events – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 102: Verify loop 3.6.7: history

Advertising
background image

102

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Programming

Master Programming Level

Pressing 2 while viewing the Node Mode Setup Screen will allow the programmer to enter the
address of the node on the Lite-Connect circuit..

A flashing cursor will appear in the lower left corner of the display. Enter the two-digit address
which can be a value between 02 and 17. (Address 01 is reserved for the hub.) After the second
digit is entered, the display will return to the Node Mode Setup screen.

3.6.6 Verify Loop

Pressing 3 while viewing Programming Screen #2, will select the Verify Loop option. During loop
verification, the FACP polls each device on the SLC to determine if the device is communicating
and whether or not it responds with the proper type identification. The following screen will be
displayed while verification is in progress:

When Loop verification has been completed, the display will indicate that the system is OK or, if
problems have been detected, any device type programming errors. Use the up and down arrow
keys to view all detected errors.

3.6.7 History

The History option allows an authorized user to view or erase events which have occurred in the
control panel. Pressing 1 while viewing Programming Screen #3 will display the History options
as shown in the following display:

View Events

Pressing 1 while viewing the History Screen will allow the user to select the events to be viewed as
illustrated in the following:

While displaying the View Events screen, press 1 to view all events, 2 to view only alarms or 3 to
view other events. Use the up and down arrow keys to scroll through all of the displayed events.

NODE ADDRESS

ENTER NODE ADDRESS

RANGE 02-17

Node Mode Setup Screen

PROGRAMMING

1=LOOP SETUP

2=SYSTEM SETUP

3=VERIFY LOOP

Programming Screen #2

VERIFYING LOOPS

PLEASE WAIT

Verification Progress Screen

PROGRAMMING

1=HISTORY

2=WALKTEST

3=OPTION MODULES

Programming Screen #3

HISTORY

1=VIEW EVENTS

2=ERASE HISTORY

History Screen

HISTORY

1=VIEW EVENTS

2=ERASE HISTORY

History Screen

HISTORY

1=VIEW ALL

2=VIEW ALARMS

3=VIEW OTHER EVENTS

View Events Screen