8 digital communicator, Digital communicator, Figure 2.14 wiring phone jacks – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 38

Advertising
background image

38

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Installation

Digital Communicator

2.8 Digital Communicator

Two independent telephone lines can be connected to the control panel. Telephone line con-
trol/command is made possible via double line seizure as well as usage of an RJ31X style intercon-
nection. Note that it is critical that the panel's digital communicator be located as the first device
on the incoming telephone circuit to properly function.
Important! The DACT must not be used to dial a phone number that is call-forwarded.

The control panel's digital communicator is built into the main circuit board. Connection and wir-
ing of two phone lines is required as shown below.

Figure 2.13 DACT Installation

Customer Premises Equipment and Wiring

Telephone

Line

FACP with DACT

Network

Service

Provider’s

Facilities

Network

Demarcation

Point

RJ31X

Jack

Unused

RJ-11 Jack

Unused

RJ-11 Jack

Telephone

Telephone

Telephone

Answering

System

Fax Machine

Computer

a

c

ta

d

a

c

t.

c

d

r

1 2 3 4 5 6 7

7

8

1 2 3 4 5 6

8

KISSOFF

PRI. ACTIVE

SEC. ACTIVE

SEC. PHONE LINE

PRI. PHONE LINE

J15

J16

Figure 2.14 Wiring Phone Jacks

Ring

Tip

To premise phones

Ring

Tip

Green Wire

Red Wire

Ring

Tip Green Wire

Red Wire

(Secondary Lines)
Incoming Telco Phone Lines

Ring

Tip

To premise phones

(Primary Lines)
Incoming Telco Phone Lines

RJ31X

Jack

RJ31X

Jack

Note: Shorting

bars inside RJ31X

Jack removed

during installation.

7 foot Cable

MCBL-7

(ordered

separately)

Primary Phone
Line PH1

Secondary
Phone Line
PH2

Module Female
Connectors

Male Plug

Connectors

Ferrite Clamps (see Section 2.8.1)

9