Ar function block, 1 ar function block schematic, Ar function block -1 – Yokogawa YVP110 User Manual

Page 100: Ar function block schematic -1

Advertising
background image

<18. AR Function Block>

18-1

IM 21B04C01-01E

18. AR Function Block

The Arithmetic (AR) block switches two main inputs of different measurement ranges seamlessly and

combines the result with three auxiliary inputs through the selected compensation function (10 types) to

calculate the output.

18.1 AR Function Block Schematic

The diagram below shows the Arithmetic block schematic.

F1801.ai

Figure 18.1 AR Block

The Arithmetic block is divided into three sections:

• Input section: Makes a go/no-go decision on the use of an input value, switches the range, and determines

the PV status.

• Computation section: Makes calculations through ARITH_TYPE.

• Output section: Applies gain multiplication and bias addition to the calculated result to perform limitation

processing for output.

* The range extension function compensates the IN and IN_LO input values when two devices with different ranges are connected, to

make smooth input switching.