Caution – Yokogawa YVP110 User Manual

Page 36

Advertising
background image

<5. Setup>

5-3

IM 21B04C01-01E

The tuning result will be written to AUTO_

TUNE_RESULT. The value of AUTO_TUNE_

RESULT is 255 and is displayed as “In

operation” while auto tuning is running, and will

change to 1 which is displayed as “Succeeded”

when auto tuning has finished successfully. In

the event of a warning or error, a value other

than those below will be displayed. For details,

see the specifications for the transducer block.

1 = succeeded

2 = canceled

255 = in operation

The values of the hysteresis of valve actions

and the air supply pressure measured during

auto tuning are stored in parameters of the

transducer block inside the YVP110. Note that

pressure data such as air supply pressure data

are available only for a YVP110 with an optional

pressure sensor.

CAUTION

Ensure that the pressure of the air supply to

the YVP110 positioner is regulated within the

specified range. If it differs from the pressure

during actual operation, or if it is unstable,

optimum tuning results may not be obtained.

The following parameters are tuned by carrying out

auto tuning: (For details, see secction A6.4)

SERVO_GAIN

(static loop gain of internal valve control loop)

SERVO_RESET (integral time)

SERVO_RATE (derivative time)

SERVO_RATE_GAIN (derivative gain)

SERVO_DEADBAND

(dead band of integral action)

SERVO_OFFSET (offset of integral action)

BOOST_ON_THRESHOLD

(threshold to switch on the boost action)

BOOST_OFF_THRESHOLD

(threshold to switch off the boost action)

BOOST_VALUE

SERVO_I_SLEEP_LMT

(timer setting for integral action)

SERVO_P_ALPHA

(multiplication coefficient for the square of

proportional factor)

INTERNAL_GAIN

(total gain of I/P module,control relay and the

valve)

X_BST_ON_THRESHOLD *

(the addition value to threshold for switching

on boost action for exhaust.)

X_BST_OFF_THRESHOLD *

(the addition value to threshold for switching

off boost action for exhaust)

X_BOOST_VALUE *

(the addition boost value for exhaust)

*Applicable only for Double Acting Type

Normally, control parameters need not be

readjusted after auto tuning. (Should there be a

problem, see Chapter 16, “Troubleshooting.”)

If you want to carry out fine adjustments of the

zero-point and span settings, perform the travel

calibration as follows.

l

Travel Calibration

If the full stroke of the valve is too large for the

maximum required flow rate, you can change

the span of the travel by carrying out a travel

calibration.
(1) First, vary the value of FINAL_VALUE.value

(see caution) to move the stem and adjust the

stem to the desired point that you want to set as

the 100% position.

(2) Next, write 3 to TRAVEL_CALIB_EXEC. This

changes the span while leaving the zero point

unchanged.
TRAVEL_CALIB_EXEC:

1 = off

2 = 0%-point calibration (no change to span)

3 = span calibration (no change to 0% point)

4 = 50%- point calibration

(no change to either span or 0% point)

CAUTION

Only when the target mode's in both the AO and

transducer blocks are O/S, can FINAL_VALUE.

value be written.

The result of the travel calibration will be written to

TRAVEL_CALIB_RESULT.