<1. Notes on Handling>

1-6

IM 21B04C01-01E

Note 2. Wiring

• All wiring shall comply with National Electrical

Code ANSI/NEPA70 and Local Electrical

Codes.

• “FACTORY SEALED, CONDUIT SEAL NOT

REQUIRED.”

Note 3. Operation

• Note a warning label worded as follows;

WARNING: OPEN CIRCUIT BEFORE

REMOVING COVER.

• Take care not to generate mechanical spark

when accessing to the instrument and

peripheral devices in hazardous locations.

Note 4. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void

the approval of Factory Mutual Research

Corporation.

C) FM Nonincendive approval
Model YVP110 Advanced Valve Positioner with

optional code /FN15.

• Applicable standard: FM3600, FM3611,

FM3810

• Nonincendive Approval

Class I, Division 2, Groups A, B, C and D

Class II, Division 2, Groups F and G

Class III, Division 1 and

Class I, Zone 2, Group IIC in Hazardous

(Classified) Locations.

Temperature Class: T4

Ambient Temperature: –40 to 60°C

Enclosure: NEMA Type4X

• Electrical Parameters:

Vmax = 32 Vdc

Ci = 1.76 nF

Li = 0 µ H

• Caution for FM Nonincendive type.

(Following contents refer to “DOC. No.

NFM010-A12 p.1 and p.2”)

NFM010-A12

Installation Diagram:

Safe Area

Hazardous Area

F0105.ai

Terminator

Nonincendive

Power Supply

Field Instruments

YVP

Valve Positioner

Field Instruments

+

+

+

Note 1.

Dust-tight conduit seal must be used when

installed in Class II and Class III environments.

Note 2.

Installation should be in accordance with

National Electrical Code (ANSI/NFPA 70)

Sections 504, 505 and Local Electrical Code.

Note 3.

The configuration of Associated Apparatus must

be Factory Mutual Research Approved.

Note 4.

Associated Apparatus manufacturer's

installation drawing must be followed when

installing this equipment.

Note 5.

No revision to drawing without prior Factory

Mutual Research Approval.

Note 6.

Terminator and supply unit must be FM

approved.

Note 7.

Installation requirements;

Vmax ≥ Voc or Vt

Ca ≥ Ci + Ccable

La ≥ Li + Lcable