<17. IS Function Block>

17-10

IM 21B04C01-01E

When SELECT TYPE is “Average”
The block calculates the average of the valid inputs and transmits it to OUT. The number of inputs used to

calculate its value is indicated in SELECTED.

SELECTION

IN_1 = 23

SELECT_TYPE = Average

STATUS_OPTS

MIN_GOOD = 1

SELECTED = 8

OUT = 25.48

(IN_1+···+IN_8)/8 = 25.48

IN_2 = 34.5

IN_3 = 45

IN_4 = 2.34

IN_5 = 23.6

IN_6 = 15.5

IN_7 = 32.5

IN_8 = 27.4

DISABLE_1 = OFF

DISABLE_2 = OFF

DISABLE_3 = OFF

DISABLE_4 = OFF

DISABLE_5 = OFF

DISABLE_6 = OFF

DISABLE_7 = OFF

DISABLE_8 = OFF

OP_SELECT = 0

F1709.ai

Figure17.9 Example (8)

When SELECT TYPE is “Latched Good”
The valid input with the smaller input number is selected as an output and is held until it becomes invalid.

When it becomes invalid, the next valid input will be selected as an output regardless of the magnitude of the

value. Even if an input with the input number smaller than that of the currently selected input recovers, the

current selection is held.
Assuming that IN_2 is the valid input with the smallest input number, the order of input selection is IN_2 →

IN_3 → ...→ IN_8 → IN_1 → ....
If the power is turned OFF and then ON with SELECT TYPE set to “Latched Good,” input selection starts with

the IN that was selected before the power was turned OFF.