<5. Setup>

5-5

IM 21B04C01-01E

(4) Thresholds for Limit Switches

Just like hardware limit switches for a valve,

on/off status signals can be generated when

the valve position read-back signal FINAL_

POSITION_VALUE.value reaches specified

levels. These on/off statuses can be transferred

to a DI function block.

Write the threshold for the upper limit switch to

LIMSW_HI_LIM, and the threshold for the lower

limit switch to LIMSW_LO_LIM.

A hysteresis of 1% is applied to the thresholds,

LIMSW_HI_LIM and LIMSW_LO_LIM.

CAUTION

To make a DI block read the on/off statuses of a

limit switch, set CHANNEL of the DI block to:

• 2, for reading the on/off status of the upper

limit switch.

• 3, for reading the on/off status of the lower

limit switch.

(5) Thresholds for Operation Result Integration

Alarms

The YVP110 has a function to integrate the

following operation result quantities individually:

• TOTAL_CYCLE_COUNT (incremented by 1

at each change in the direction of the action)

• TOTAL_TRAVEL (in % where full stroke =

100%)

• TOTAL_OPEN_TIME (in hours)

• TOTAL_CLOSE_TIME (in hours)

• TOTAL_NEAR_CLOSE_TIM (total at nearly

closed time in hours)

• SERVO_WARN_COUNT (Total number of

times of Servo output drift warning)

When these values exceed the respective

thresholds below, corresponding alarms are

output. Set the thresholds as necessary.

• CYCLE_COUNT_LIM

• TRAVEL_LIM

• OPEN_TIME_LIM

• CLOSE_TIME_LIM

• NEAR_CLOSE_TIME_LIM
Also, set NEAR_CLOSE_THRESHOLD,

which defines the threshold of the valve

position for counting NEAR_CLOSE_TIME,

as necessary.

For other alarms and self-diagnostic

functions, see “12.6 Online Diagnostics”.