<1. Notes on Handling>

1-10

IM 21B04C01-01E

Note 7. Ex ic Installation

• All wiring shall comply with local installation

requirements (refer to the installation

diagram)

F0108.ai

Valve Positioner

Installation Diagram

Hazardous Area

Non-hazardous Area

Associated Apparatus

+

+

Electrical Data: Ui = 32 V

Ci = 3.52 nF

Li = 0 μH

Note 8. Ex ic Specific Conditions of Use

WARNING

• Electrostatic charge may cause an explosion

hazard. Avoid any actions that cause the

generation of electrostatic charge, such as

rubbing with a dry cloth on coating face of

product.

• When the lightning protector option is

specified (/A), the apparatus is not capable

of withstanding the 500V insulation test

required by EN60079-11. This must be taken

into account when installing the apparatus.

• WHEN THE AMBIENT TEMP.≥70°C, USE

THE HEAT-RESISTING CABLE AND

CABLE GRAND≥90°C

• POTENTAIAL ELECTROSTATIC

CHARGING HAZARD – SEE USER’S

MANUAL

Note 9. Ex nA Installation

• Screws of terminals for field wiring

connections shall be tightened with specified

torque values: 1.2 N·m

WARNING

When using a power supply not having a

nonincendive circuit, please pay attention not to

ignite in the surrounding flammable atmosphere.

In such a case, we recommend using wiring

metal conduit in order to prevent the ignition.

Note 10. Ex nA Specific Conditions of Use

WARNING

• Electrostatic charge may cause an explosion

hazard. Avoid any actions that cause the

generation of electrostatic charge, such as

rubbing with a dry cloth on coating face of

product.

• WHEN THE AMBIENT TEMP.≥70°C, USE

THE HEAT-RESISTING CABLE AND

CABLE GRAND≥90°C

• POTENTAIAL ELECTROSTATIC

CHARGING HAZARD – SEE USER’S

MANUAL

• DO NOT OPEN IN AN EXPLOSIVE

ATMOSPHERE WHEN ENERGIZED

(2) Electrical Connection
The type of electrical connection is stamped near

the electrical connection port according to the

following marking.

Location of the marking

Screw Size

Marking

ISO M20

×

1.5 female

ANSI 1/2 NPT female

M
N

F0109.ai

(3) Installation

WARNING

All wiring shall comply with local installation

requirement and local electrical code.