<Appendix 1. Function Block Parameters>

A-10

IM 21B04C01-01E

A1.4 Parameters of DI Block

Relative

Index

Index

Parameter

Name

Default

(factory

setting)

Write

Description

DI1

DI2

0

6000 6100 BLOCK

HEADER

Block tag

= O/S

Information about this block, including the block tag, DD

revision, execution time.

1

6001 6101 ST_REV

0

Incremented when a change is made to the parameter settings

for the DI block to indicate the revision level of the settings, and

used to see whether there is a change in parameter settings.

2

6002 6102 TAG_DESC Spaces

Universal parameter storing the description of the tag.

3

6003 6103 STRATEGY 1

Universal parameter used by an upper-level system to classify

the function blocks.

4

6004 6104 ALERT_KEY 1

Universal parameter used as a key to identify the point from

which an alert is issued; normally used by an upper-level

system to select alerts to provide to a particular operator who

covers a specific area of the plant.

5

6005 6105 MODE_BLK O/S

Universal parameter that indicates the block operation

conditions and is composed of actual mode, target mode,

permitted modes, and normal mode.

6

6006 6106 BLOCK_

ERR

Indicates the error statuses related to the block itself.

7

6007 6107 PV_D

Indicates the primary discrete value (or the corresponding

process value) used to execute the specified actions, and the

status of that value.

8

6008 6108 OUT_D

Man

Indicates the output value and its status.

9

6009 6109 SIMULATE_

D

disable

Used to determine whether to use the limit switch signal input

from the transducer block or use the user-set value. When

this parameter is set to disable, the block uses the actual input

value and status.

10

6010 6110 XD_STATE

0

Index to the text describing the states of the discrete value

obtained from the transducer, but not supported by YVP110.

11

6011 6111 OUT_STATE 0

Index to the text describing the states of a discrete output, but

not supported by YVP110.

12

6012 6112 GRANT_

DENY

0

Used to check whether various user operations can be put

into effective. Before operations, in the GRANT parameter

component, set the bits (to 1) corresponding to the intended

operations. After the operations, check the DENY parameter

component. If the corresponding bits are not set (to 1) in

DENY, it proves that the corresponding operation has been put

into effective.

13

6013 6113 IO_OPTS

0

O/S

Settings for the I/O processing of the block.

14

6014 6114 STATUS_

OPTS

0

O/S

Defines block actions depending on block status conditions.

15

6015 6115 CHANNEL

2 or 3

O/S

Defines the channel number of the hardware channel

connected to the transducer block. Always set 2 for the DI1

block and 3 for DI2 in a YVP110.

16

6016 6116 PV_FTIME

0 second

Time constant of filter for PV_D.

17

6017 6117 FIELD_VAL_

D

Status of limit switch signal obtained from the transducer block.

18

6018 6118 UPDATE_

EVT

Shows the contents of an update event upon occurrence.

19

6019 6119 BLOCK_

ALM

Shows the contents of a block alarm upon occurrence.

20

6020 6120 ALARM_

SUM

enable

Shows the alarm summary (current alarm statuses,

acknowledged/unacknowledged states, masking states) for

the DI block.

21

6021 6121 ACK_

OPTION

0xFFFF

Defines the priority of WRITE_ALM as well as allows for

notification to be disabled and makes acknowledement

unnecessary for WRITE_ALM .

22

6022 6122 DISC_PRI

0

Priority order of discrete alarm.

23

6023 6123 DISC_LIM

1

Input status of generating a discrete alarm.

24

6024 6124 DISC_ALM

Status of discrete alarm.