A1.3 parameters of ao block, A1.3 – Yokogawa YVP110 User Manual

Page 119

Advertising
background image

<Appendix 1. Function Block Parameters>

A-8

IM 21B04C01-01E

Relative

Index Index

Parameter Name

Default

(factory setting)

Write

Description [Setting range]

104

2104 SIGN_DATA_Y

0

Parameter used to upload the measured

signature data (output data).

105

2105 SIGN_MEAS_DATE 01/01/00

00:00:00.000

Parameter used to upload the date and time of

signature measurement

106

2106 SIGN_HEADER_

DATA

+inf

Parameter used to upload the ambient

temperature and settings at signature

measurement

107

2107 STD_ACT_SIGN_

SET

180, 180, 50

Settings of the standard actuator signature

108

2108 EXT_ACT_SIGN_

SET

0, 100, 180, 180,

50, 200

Settings of the extended actuator signature and

high-resolution actuator signature

109

2109 STEP_RESP_SET

45, 55, 100, 600

Settings of step levels for step response test

110

2110 POSITIONER_

SIGN_SET

0, 100, 10, 30,

30

Settings of the positioner signature

111

2111 SERVO_WARN_HI_

LIM

80 % of MV

High-limit alarm setting for Servo Output Drift

warning

112

2112 SERVO_WARN_LO_

LIM

20 % of MV

Low-limit alarm setting for Servo Output Drift

warning

113

2113 SERVO_TIME_TH

10 sec

High-limit alarm setting for total time of Servo

Output Drift warning.

114

2114 SERVO_WARN_

COUNT

0

O/S

Total number of times of Servo Output Drift

warning. To reset the count, write 0.

115

2115 X_BST_ON_

THRESHOLD

0, 0 %

O/S

The addition value to threshold for switching on

boost action; a control parameter for exhaust [-10

to 10%] Applicable for Double Acting Type

116

2116 X_BST_OFF_

THRESHOLD

0, 0 %

O/S

The addition value to threshold for switching off

boost action; a control parameter for exhaust [-10

to 10%] Applicable for Double Acting Type

117

2117 X_BOOST_VALUE

0, 0 % of MV

O/S

The addition Boost value; a control parameter

for exhaust [-50 to 50%] Applicable for Double

Acting Type

A1.3 Parameters of AO Block

Relative

Index Index

Parameter Name

Default

(factory setting)

Write

Description

0

5000 BLOCK HEADER

Block tag

= O/S

Information about this block, including the block

tag, DD revision, execution time.

1

5001 ST_REV

0

Incremented when a change is made to the

parameter settings for the AO block to indicate

the revision level of the settings, and used to see

whether there is a change in parameter settings.

2

5002 TAG_DESC

Spaces

Universal parameter storing the description of the

tag.

3

5003 STRATEGY

1

Universal parameter used by an upper-level

system to classify the function blocks.

4

5004 ALERT_KEY

1

Universal parameter used as a key to identify

the point from which an alert is issued; normally

used by an upper-level system to select alerts

to provide to a particular operator who covers a

specific area of the plant.

5

5005 MODE_BLK

O/S

Universal parameter that indicates the block

operation conditions and is composed of actual

mode, target mode, permitted modes, and normal

mode.

6

5006 BLOCK_ERR

Indicates the error statuses related to the block

itself.

7

5007 PV

Indicates the primary analog value (or the

corresponding process value) used to execute the

specified actions, and the status of that value.