<10. Actions of YVP110 During Operation>

10-3

IM 21B04C01-01E

Table 10.3

Alert Objects

Subindex

Parameter

Name

Description

An

al

og

A

le

rt

D

is

cr

et

e

Al

er

t

U

pd

at

e

Al

er

t

1 1 1 Block Index Leading Index to the block in

which the alert has occurred

2 2 2 Alert Key

Copy of ALERT_KEY

3 3 3 Standard

Type

Type of the alert that occurred

4 4 4

Mfr Type

The name of the alert defined

in the device description

(DD) file written by the device

manufacturer.

5 5 5 Message

Type

Cause of the alert

6 6 6 Priority

Priority level of the alert

7 7 7 Time Stamp Time when the alert occurred

first

8 8

Subcode

Subcode that indicates the

cause of the alert

9 9

Value

Value of the related data

10 10

Relative

Index

Relative Index to the related

data

8 Static

Revision

Value of ST_REV in the block

11 11 9 Unit Index

Unit code of the related data

10.3 Simulation Function

The YVP110 has a function to simulate input

signals to its internal function blocks and makes the

blocks to carry out the specified actions with the

simulated input signals in order to allow for testing

applications in the host computer or alarm handling

processes. Each function block has a parameter

to switch on/off the simulation function. To prevent

this parameter setting from being modified during

plant operation by mistake, a hardware switch

labeled SIM.ENABLE is provided on the YVP110’s

amplifier assembly. Sliding this switch position

to ON enables the simulation function to run.

Remotely writing “REMOTE LOOP TEST SWITCH”

to SIM_ENABLE_MSG also causes the same

effect as turning ON the SIM.ENABLE switch;

however, the value of SIM_ENABLE_MSG will

be lost when the power to the YVP110 is turned

off. In short, simulation can be carried out if the

hardware SIM.ENABLE switch is ON or if the value

of SIM_ENABLE_MSG is “REMOTE LOOP TEST

SWITCH”.
When the simulation can be carried out, alarms

generated from the resource blocks mask the other

device alarms. Hence, simulation must be disabled

immediately after it has finished.

F1001.ai

1
2

O

N

Normally OFF
Unused

SIM.ENABLE switch

Figure 10.1 SIM.ENABLE Switch