<Appendix 1. Function Block Parameters>

A-12

IM 21B04C01-01E

A1.6 Parameters of PID Block (Optional)

Index: PID1: 8000 through 8065

PID2: 8100 through 8165

Relative

Index Index

Parameter

Name

Default

(factory setting)

Write

Description

0

8000 BLOCK

HEADER

Block tag

= O/S

Information about this block, including the block tag, DD

revision, execution time.

1

8001 ST_REV

0

Incremented when a change is made to the parameter

settings for the PID block to indicate the revision level of

the settings, and used to see whether there is a change

in parameter settings.

2

8002 TAG_DESC

Spaces

Universal parameter storing the description of the tag.

3

8003 STRATEGY

1

Universal parameter used by an upper-level system to

classify the function blocks.

4

8004 ALERT_KEY 1

Universal parameter used as a key to identify the point

from which an alert is issued; normally used by an upper-

level system to select alerts to provide to a particular

operator who covers a specific area of the plant.

5

8005 MODE_BLK

O/S

Universal parameter that indicates the block operation

conditions and is composed of actual mode, target

mode, permitted modes, and normal mode.

6

8006 BLOCK_ERR —

Indicates the error statuses related to the block itself.

7

8007 PV

Indicates the primary analog value (or the corresponding

process value) used to execute the specified actions,

and the status of that value.

8

8008 SP

Auto

Setpoint of the block.

9

8009 OUT

Man

Value and status of output.

10

8010 PV_SCALE

0-100%

O/S

Upper and lower scale limit values used for scaling of the

input (IN) value.

11

8011

OUT_SCALE 0-100%

O/S

Upper and lower scale limit values used for scaling

of the control output (OUT) value to the values in the

engineering unit.

12

8012 GRANT_

DENY

0

Option to control access from the host computer and

local control panel to tuning and alarm parameters.

13

8013 CONTROL_

OPTS

0x0000

O/S

Defines block actions depending on block status

conditions.

14

8014 STATUS_

OPTS

0x0000

O/S

Defines options for control actions of block.

15

8015 IN

0

Controlled-value input.

16

8016 PV_FTIME

0

Time constant (in seconds) of the first-order lag filter

applied to IN.

17

8017 BYPASS

1

Man

Determines whether to bypass control computation.

1 = off; do not bypass.

2 = on; bypass.

18

8018 CAS_IN

0

Cascade setpoint.

19

8019 SP_RATE_

DN

+INF

Rate-of-decrease limit for setpoint (SP).

20

8020 SP_RATE_UP +INF

Rate-of-increase limit for setpoint (SP).

21

8021 SP_HI_LIM

100

Upper limit for setpoint (SP).

22

8022 SP_LO_LIM

0

Lower limit for setpoint (SP).

23

8023 GAIN

1

Proportional gain (= 100 / proportional band).

24

8024 RESET

10

Integration time (seconds).

25

8025 BAL_TIME

0

Unused.

26

8026 RATE

0

Derivative time (seconds).

27

8027 BKCAL_IN

0

Readback of control output.

28

8028 OUT_HI_LIM 100

Upper limit for control output (OUT).

29

8029 OUT_LO_LIM 0

Lower limit for control output (OUT).

30

8030 BKCAL_HYS 0

Hysteresis for release from a limit for OUT.status.

31

8031 BKCAL_OUT —

Read-back value to be sent to the BKCAL_IN of the

downstream block.

32

8032 RCAS_IN

0

Remote setpoint set from the host computer.