<12. Transducer Block>

12-5

IM 21B04C01-01E

12.6.2 Fail-safe Action

If the “A/D converter failure,” “position sensor

failure,” or “deviation error” event occurs in the

XD_ERROR described above, the transducer block

activates the specified fail-safe action by cutting the

current signal to I/P module to zero. In addition, in

the event of “position sensor failure” or “deviation

error,” the fail-safe action will not be deactivated

even when the cause of the failure/error is

cleared. Writing “Clear non-latch” to the parameter

RELEASE_FAILSAFE will finally deactivate the

fail-safe action in this case. The fail-safe action

activated in the event of “A/D converter failure” will

be deactivated automatically when the cause of the

failure is cleared.

12.6.3 Operation Result Integration

The YVP110 has a function to integrate the

following operation result quantities individually.

To reset an integrated quantity, write 0 to the

corresponding parameter.

• TOTAL_CYCLE_COUNT:

Incremented by 1 at each change in the

direction of the valve action and indicates the

total number of times of changes in direction of

valve actions.

• TOTAL_TRAVEL:

Total travel distance of the stem position shown

as a percentage of the valve position span.

• TOTAL_OPEN_TIME and TOTAL_CLOSE_

TIME:

TOTAL_CLOSE_TIME contains the integrated

time periods (in hours) when the valve position

is equal to or less than the thresholds previously

set in OPEN_CLOSE_THRESHOLD. TOTAL_

OPEN_TIME is the integrated time periods (in

hours) other than TOTAL_CLOSE_TIME.

• TOTAL_NEAR_CLOSE_TIM:

Total time period (in hours) when the valve

position is within the threshold set in NEAR_

CLOSE_THRESHOLD.

• SERVO_WARN_COUNT:

Total number of times the servo output drift

warning occurred.

Indicates the total number of times a drift

warning occurred regarding the output current

to the I/P module.

12.6.4 Recording of Revisions

When the user makes a change to the setting of a

static parameter, the change is counted-up in the

parameter ST_REV and update event is generated.

12.7 Control Parameters

The following control parameters in a YVP110 can

be set up by auto tuning: (For details, see section

A6.4)

SERVO_GAIN

SERVO_RESET

SERVO_RATE

SERVO_RATE_GAIN

SERVO_DEADBAND

SERVO_OFFSET

BOOST_ON_ THRESHOLD

BOOST_OFF_THRESHOLD

BOOST_VALUE

SERVO_I_SLEEP_LMT

SERVO_P_ALPHA

INTERNAL_GAIN

X_BOOST_ON_THRESHOLD *

X_BOOST_OFF_THRESHOLD *

X_BOOST_VALUE *
* Applicable only for Double Acting Type

12.8 Temperature and Pressure

Measurement

The YVP110 measures the surface temperature

of the amplifier and sets it in the parameter

ELECT_TEMP in the transducer block. The unit of

temperature is defined by TEMPERATURE_UNIT

and can be selected from:

1001 = °C

1002 = °F

A YVP110 with an optional pressure sensor can

measure the output air pressure to the valve

actuator and sets it in the parameter OUT_

PRESSURE. The unit of pressure is defined

by Unit Code in SPRING_RANGE and can be

selected from:

1133 = kPa

1137 = bar

1141 = psi

1145 = kgf/cm

2