<1. Notes on Handling>

1-9

IM 21B04C01-01E

I.S. values Power supply-field device:

Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii

Calculation of max. allowed cable length:

Ccable ≤ Co - ∑ci - ∑ci (Terminator)

Lcable ≤ Lo - ∑Li

Number of Devices
The number of devices (max. 32) possible on a

fieldbus link depends on factors such as the power

consumption of each device, the type of cable used,

use of repeaters, etc.
B) ATEX Flameproof Type
Caution for ATEX flameproof type.
Note 1. Model YVP110 Valve Positioner with

optional code /KF2 is applicable for

potentially explosive atmospheres:

• Applicable standard:

EN60079-0:2009, EN60079-1:2007

• Certificate: KEMA 10ATEX0023 X

• Group: II

• Category: 2G

• Type of Protection and Marking Code:

Ex d IIC, T6 or T5 Gb

• Ambient Temperature: T6; –40 to 65°C

T5; –40 to 80°C

Note 2. Electrical Data

• Supply voltage: 32 V DC max.

• Output signal: 17 mA DC

Note 3. Installation Instructions

• The cable glands and blanking elements

shall be certified in type of protection

flameproof enclosure “d” suitable for the

conditions of use and correctly installed.

• With the use of conduit entries a sealing

device shall be provided either in the

flameproof enclosure or immediately on the

entrance thereto.

• To maintain the degree of ingress protection

IP65 according to EN 60529 special care

must be taken to avoid water entering the

breathing and draining device when the valve

positioner is mounted with the feedback shaft

in the upright position.

Note 4. Operation

• Keep strictly the WARNING on the label on

the positioner.

AFTER DE-ENERGIZING, DELAY 5

MINUTES BEFORE OPENING.

WHEN THE AMBIENT TEMP. ≥ 70°C,

USE HEAT-RESISTING CABLE & CABLE

GLAND ≥ 90°C.

Note 5. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void KEMA
Flameproof Certification.

C) ATEX Intrinsically safe (Ex ic)/Type n (Ex nA)

Note 1. Model YVP110 Advanced Valve Positioner

with optional code /KN25

• Applicable standard:

EN60079-0:2009/EN60079-0:2012(Ex ic/Ex

nA), EN60079-11:2012(Ex ic)

EN60079-15:2010(Ex nA)

• Ex ic: II 3G Ex ic IIC T4 Gc (Intrinsically safe)

• Ex nA: II 3G Ex nA IIC T4 Gc (Non-sparking)

• Ambient Temperature: -30 to 75°C

• Ambient Humidity:

0 to 100%RH (No condensation)

• Enclosure: IP65

• Installation category: I

Note 2. Electrical Data

• Ex ic: Ui = 32 V, Ci = 3.52 nF, Li = 0 μH

• Ex nA: 32 V DC MAX

Note 3. For the installation of this positioner, once

a particular declared type of protection

is selected, the other type of protection

cannot be used. The installation must be in

accordance with the description about type

of protection in this instruction manual.

Note 4. In order to avoid confusion, unnecessary

marking is crossed out on the label other

than the selected type of protection when

positioner is installed.

Note 5. Installation Instructions

• Cable glands, adapters and/or blanking

elements shall be of Ex “n”, EX “e” or Ex “d”

and shall be installed so as to maintain the

specified degree of protection (IP Code) of

the equipment.

• To maintain the degree of protection IP65

according to IEC 60529, special care must

be taken to avoid water.

Note 6. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void ATEX

Ex ic and Ex nA.