<12. Transducer Block>

12-1

IM 21B04C01-01E

12. Transducer Block

12.1 General

The transducer block works as an interface

between the hardware I/O (actuator, sensor) and

internal function blocks. Most functions of the

YVP110 as a valve positioner are packed in the

transducer block. Major functions of the transducer

blocks include:

• Transmission and reception of setpoint and

readback signals for valve position

• Setpoint high/low limiters

• Auto tuning

• Valve tight-shut and full-open actions

• Valve position-to-flow rate characteristics

conversion

• Travel calibration

• Diagnostics of valve and positioner

• Valve position limit switches

• Pressure and temperature measurement

(pressure measurement requires the optional

sensor)

• Fail safe

The transducer block in a YVP110 is connected

to an AO function block and two DI blocks via its

channels as shown below.

Table 12.1

Correspondence between Channels

and I/O Signals

Channel

Signal

Description

1

Analog input/output Setpoint and readback

signals

2

Discrete output

High limit switch status

3

Discrete output

Low limit switch status

12.2 Forward Path

The following describes the signal input from the

AO block to the transducer block and then passed

to the device hardware side.

12.2.1 Input from AO Block

The OUT value of the AO block is input to the

transducer block. This input action is halted when:

• The channel number of the AO block is not set

as 1; or

• The AO block is in O/S mode.

Based on the input value from the AO block,

transducer block:

• Performs the flow rate-to-valve position

conversion;

• Limits the setpoint within a specified range; and

• Performs tight-shut or full-open action as

necessary.

The input from the AO block is always a percentage

value where the transducer block always

regards 0% to be the shut-off position. Make

the correct settings at initial setup according to

the specifications of the valve (in reference with

Chapter 5, “Setup”).

F1201.ai

CHANNEL1

FINAL_VALUE

Final Value

POSITION_CHAR_TYPE

POSITION_CHAR

CHANNEL1

FINAL_POSITION_VALUE

AO Readback

POSITION_CHAR_TYPE

POSITION_CHAR

CHANNEL3

CHANNEL2

Limit Switch

LIMSW_HI_LIM

LIMSW_LO_LIM

Limiter

FINAL_VALUE

_RANGE

Tight Shutoff / Full Open

FINAL_VALUE_CUTOFF_HI

FINAL_VALUE_CUTOFF_LO

Figure 12.1 Function Diagram of Transducer Block