<5. Setup>

5-4

IM 21B04C01-01E

5.4 Checking Valve Actions

After carrying out auto tuning, check step

responses by changing the value of the transducer

block's final valve position setpoint, FINAL_VALUE.

value. Also, check whether the valve acts correctly

over the 0-100% position range.

NOTE

Only when the target mode is in MODE_BLK

parameters in both the AO and transducer blocks

are O/S, can FINAL_VALUE.value be written.

It is not usually necessary to readjust the control

parameters after auto tuning. However, when

using the Double Acting Type or if the expected

response characteristics cannot be obtained

using auto tuning, either conduct manual tuning

in reference to APPENDIX 6 or refer to Section

18.5 Troubleshooting Auto Tuning.

5.5 Setting Parameters of

Transducer Block

Set the following parameters as necessary. For the

settings made as default when shipped, see the

parameter lists in Appendix 1.
(1) Position-to-flow Rate Characteristic Type

The parameter POSITION_CHAR_TYPE

defines the characteristics between the valve

position and flow rate, and is set to linear by

default. Write the appropriate value:

1 = linear

2 = equal percent (50:1)

3 = equal percent (30:1)

4 = quick open (reversal of equal % - 50:1)

5 = Camflex Percentage

255 = user-defined

Writing the value 255 allows you to define the

desired characteristics by 10 line segments for

evenly divided input levels. The coordinates

(0,0) and (100,100) are fixed; set the values

corresponding to OUT(Output of AO block) =

10%, 20%, 30%..., 80%, 90%. Note that a set

value must be greater than the preceding set

value; the output must increase as the input

increases.

F0502.ai

(1)

(4)

0

Output(OUT) of AO block

Valve position

(3)

(2)

(5)

(1) Linear

(2) Equal % (50 : 1)

(3) Equal % (30 : 1)

(4) Quick Open

(5) Camflex Percentage

Figure 5.2

Position-to-flow Rate Characteristic

Type

(2) Final-value Limits

Eu_100 and Eu_0 in the parameter FINAL_

VALUE_RANGE define the upper and lower

limits of FINAL_VALUE.value of the transducer

block.

CAUTION

Even if the range of FINAL_VALUE.value is

limited by FINAL_VALUE_RANGE, the actual

valve position is set to outside the FINAL_

VALUE_RANGE setting when the tight-shut or

full-open action described below is activated.

(3) Tight-shut and Full-open Actions

The tight-shut action is an action to decrease

the output pressure to a level much lower than

the 0% pressure level (or to increase it much

higher than the 0% pressure level for an air-

to-close valve) when FINAL_VALUE.value

is less than FINAL_VALUE_CUTOFF_LO in

order to ensure that the valve is tightly shut

off. Conversely, the full-open action is an

action to increase the output pressure to a level

much higher than the 100% pressure level (or

decrease it much lower than the 100% pressure

level for an air-to-close valve) when FINAL_

VALUE.value is larger than FINAL_VALUE_

CUTOFF_HI in order to ensure that the valve is

fully open.

A hysteresis of 1% is applied to the thresholds,

FINAL_VALUE_CUTOFF_LO and FINAL_

VALUE_CUTOFF_HI.