<Appendix 6. Manual Tuning Guideline>

A-43

IM 21B04C01-01E

If the hysteresis of a valve is large, the valve may

not react for a while after an input change, and

a delay in response may occur. This delay in

response is accompanied by a large deviation, and

the accumulation of excessive integral components

can cause an overshoot. This parameter is effective

in cases such as this.
If the deviation from the set point value exceeds the

SERVO_DEADBAND, this function starts. If 0 is set

to SERVO_DEADBAND, this function is invalid.

FA0608.ai

Set point

SERVO_DEADBAND

SERVO_DEADBAND

SERVO_I_SLEEP_LMT

Integral area

SERVO_P_ALPHA

Tuning range: 0 to 100% (Default: 0%)

Setting this parameter adds more values to the

proportional term for a large step compared to a

small step. Use this parameter when a large value

cannot be set to the proportional gain because of

the large hysteresis of a value, and the response

speed for a large step is insufficient.
A usual operation in the proportional term covers

the deviation only; however, unless 0 is set for

this parameter, a value calculated based on the

following equation is added, in addition to the

deviation. If 0 is set, this function is invalid.
(Value added to the proportional term) = deviation ×

|deviation| / SERVO_P_ALPHA
You can obtain a quadratic curve in which the

proportional term doubles when the deviation

equals the SERVO_P_ALPHA, and the added

value is in reverse proportion to an increase in the

value of SERVO_P_ALPHA.

FA0609.ai

Proportional value

Proportional + added values

Proportional value

Deviation %

10%

SERVO_P_ALPHA %

You can obtain an effect to increase the apparent

gain for a large step without changing the response

characteristics for a small step.
However, as long as the deviation is more than

10%, the added value is fixed to a value calculated

when the deviation is 10%

INTERNAL_GAIN

Tuning range: 0.5 to 50 rad/mA (Default: 5

rad/mA)

INTERNAL_GAIN is the total gain of the I/P

module, the control relay, the valve, the actuator,

and the feedback lever.
INTERNAL_GAIN is part of the loop gain of PI-D

control.
This value is usually determined by auto tuning and

travel calibration, so you do not need to change the

value.