Ao function block, 1 general, 2 modes – Yokogawa YVP110 User Manual

Page 75: 3 forward path, 1 fault state, Ao function block -1, General -1, Modes -1, Forward path -1 13.3.1, Fault state -1

Advertising
background image

<13. AO Function Block>

13-1

IM 21B04C01-01E

13. AO Function Block

13.1 General

The AO function block receives the control signal

from the transducer block and outputs it to the

actuator. The major functions of the AO function

block include:

• Scaling

• Setpoint limiters - for both the value and rate of

change

• Simulation

• Valve position feedback

• Actions upon abnormality of upstream block

• Signal inversion

The AO function block performs bi-directional signal

handling: transfer of the valve control signal to the

transducer block (forward path) and feedback of the

valve position signal from the transducer block to

the upstream block (backward path).

F1301.ai

AO

Transducer

RCAS_OUT

RCAS_IN

CAS_IN

BKCAL_OUT
OUT

Figure 13.1 Inputs/Outputs of AO Function Block

F1302.ai

Setpoint

SP_RATE_DN

SP_RATE_UP

SP_HI_LIM

SP_LO_LIM

Out Convert

PV_SCALE

XD_SCALE

Output

PV Convert

XD_SCALE

PV_SCALE

Fault State

FSTATE_TIME

FSTATE_VAL

Simulate

SIMULATE

MODE

SHED_OPT

RCAS_IN

PV

CAS_IN

OUT

CHANNEL

SP

RCAS_OUT

BKCAL_OUT

READBACK

Figure 13.2 Function Diagram of AO Function

Block

13.2 Modes

The target mode for the AO function block can be

set from five block modes: RCas, Cas, Auto, Man,

and O/S. Regardless of the target mode, the AO

block automatically enters the IMan or LO mode

when a specified condition is met (such as when

another function block enters a specific status)

depending on the parameter settings.

13.3 Forward Path

The following describes the signal input from the

upstream block to the AO block and then passed

to the transducer block. The upstream block is

typically the PID controller block, and the control

signal from the PID block is input as the source of

computing the setpoint SP for the AO block.
The path for computing the SP differs depending

on the mode. In Cas mode, CAS_IN is used for

SP. In RCas mode, RCAS_IN is used for SP. If the

value of CAS_IN or RCAS_IN, whichever is used,

is greater than SP_HI_LIM (high limit) or less than

SP_LO_LIM (low limit), the internal SP is set to the

respective limits. Also, if the rate of change in the

value of CAS_IN or RCAS_IN, whichever is used,

is greater than SP_RATE_UP (rate-of-increase

limit) in the increasing direction, or than SP_RATE_

DN (rate-of-decrease limit) in the decreasing

direction, the change in internal SP is limited by the

corresponding rate-of-change limit setting.
In RCas, Cas or Auto mode, the SP value is used

for the AO block’s output OUT, whose value is then

passed to the transducer block via channel 1.

13.3.1 Fault state

As for Fieldbus-enabled positioners including the

YVP110, not only a power failure but also other

errors (such as a communication error) can cause

the fail-safe action. For example, when the status

of the CAS_IN input of the AO block from its

upstream block indicates a specific status, such as

a communication error, the case is regarded as an

abnormality and fault state actions including a mode

change are enacted.

Advertising