<4. Wiring and Piping>

4-3

IM 21B04C01-01E

F0402.ai

Blind plug

Grounding

Input signal

Ground terminal

Figure 4.2

Wiring

(1) General-use Type and Intrinsically Safe

Type

Make cable wiring using metallic conduit or

waterproof glands.

• Apply a non-hardening sealant to the terminal

box connection port and to the threads on the

flexible metal conduit for waterproofing.

F0403.ai

Flexible metal conduit

Wiring metal

conduit

Tee

Drain plug

Apply a non-hardening

sealant to the threads for

waterproofing.

Figure 4.3

Typical Wiring Using Flexible Metal

Conduit

(2) Flameproof Type (JIS)
Wire cables through a flameproof packing adapter,

or using a flameproof metal conduit.

Wiring cable through flameproof packing

adapter for only JIS flameproof type (see Figure

4.4).

• Use only flameproof packing adapters

approved by Yokogawa.

• Apply a nonhardening sealant to the terminal

box connection port and to the threads

on the flameproof packing adapter for

waterproofing.

Flameproof packing

adapter

Flexible metal conduit

Wiring metal

conduit

Tee

Drain plug

Apply a non-hardening

sealant to the threads for

waterproofing.

F0404.ai

Figure 4.4

Typical Cable Wiring Using Flameproof

Packing Adapter

• Measure the cable outer diameter in two

directions to within 1 mm.

• Calculate the average of the two diameters,

and use packing with an internal diameter

nearest to this value (see Table 4.1).

Table 4.1

Flameproof Packings and Applicable

Cable Outer Diameters

Optional

Code

Wiring

Port thread

Diameter

Applicable

Cable OD

(mm)

Identifying

Mark

Part

Number

G11

G 1/2

8 to 10

10.1 to 12

16

16

8-10

10-12 G9601AM

• Mounting flameproof packing adapter body

to conduit connection (see Figure 4.5)