<Appendix 6. Manual Tuning Guideline>

A-42

IM 21B04C01-01E

If you manually set a value, input a value of

SERVO_OUTPUT_SIGNAL when the valve

position settles in the vicinity of 50%.

BOOST_ON_THRESHOLD [1], [2]

Tuning range: 0, 0.1 to 10% (Default: 1.9, 2.9%)

BOOST_OFF_THRESHOLD [1], [2]

Tuning range: 0.1 to 10% (Default: 1.0, 1.0%)

BOOST_VALUE [1], [2]

Tuning range: 0 to 50% of MV (Default: 8, 10%

of MV)

Set the boost function that serves as a function

for accelerating air delivery and exhaust. Tracking

capability for response after an input change

increases.
When the set point is changed, if the difference

between the old set point and the new set point is

greater than the BOOST_ON_THRESHOLD, the

BOOST_VALUE is added to the current output to

the I/P module, and the added value is removed

when the deviation enters the range of BOOST_

OFF_THRESHOLD.
However, each parameter has two values, [1] and

[2], where [1] is for a small step and [2] for a large

step. Therefore, set each parameter so that the

relation [2] ≥ [1] is established.
If the difference between the old set point and

the new set point is greater than BOOST_ON_

THRESHOLD[1] and less than [2], BOOST_

VALUE[1] functions, and the added value is

removed when the deviation enters the range of

BOOST_OFF_THRESHOLD[1].

FA0606.ai

Added to boost

BOOST_ON_THRESHOLD [2]

Added to BOOST_VALUE [1]

BOOST_ON_THRESHOLD [1]

Previous set point

Set point

Removed from BOOST_VALUE [1]

BOOST_OFF_THRESHOLD [1]

Removed from boost

If the difference between the old set point and

the new set point is greater than BOOST_ON_

THRESHOLD[2], BOOST_VALUE[2] functions

independently from BOOST_VALUE[1], and the

added value is removed when the deviation enters

the range of BOOST_OFF_THRESHOLD[2].

BOOST_ON_THRESHOLD [1]

FA0607.ai

Added to BOOST_VALUE [2]

BOOST_ON_THRESHOLD [2]

Previous Set point

Set point

Removed from BOOST_VALUE [2]

BOOST_OFF_THRESHOLD [2]

Added to boost

Removed from boost

The boost function of single-acting actuators works

only for the air supply side; however, that of double-

acting actuators also works for the exhaust side of

OUT1 (for the air delivery side of OUT2).
If you want to individually set parameters for the

exhaust side of OUT1 of double-acting actuators,

set the following parameters.

X_BST_ON_THRESHOLD [1], [2]

Tuning range: -10 to 10% (Default: 0, 0%)

X_BST_OFF_THRESHOLD [1], [2]

Tuning range: -10 to 10% (Default: 0, 0%)

X_BOOST_VALUE [1], [2]

Tuning range: -50 to 50% of MV (Default: 0, 0%

of MV)

If you want the boost function of double-acting

actuators on the exhaust side of OUT1 to be

asymmetric from the air delivery side, set these

parameters.
If you set values for these parameters, input

differences for change in relation to the values of

BOOST_ON_THRESHOLD, BOOST_OFF_

THRESHOLD, and BOOST_VALUE.
For example, if you want to stop the boost function

only on the exhaust side, input a negative value

of the absolute value of BOOST_VALUE[1] in

X_BOOST_VALUE[1], and input the value in

X_BOOST_VALUE[2] in the same way to negate

the effect. At this time, you do not need to change

the values of X_BST_ON_THRESHOLD and

X_BST_OFF_THRESHOLD.
Theses parameters are valid only for double-acting

actuators.

SERVO_I_SLEEP_LMT

Tuning range: 0 to 10 sec (Default: 0 sec)

If the deviation changes, the integration operation is

stopped for the time of SERVO_I_SLEEP_LMT to

reduce excessive integral components.