Actions of yvp110 during operation, 1 block modes, Actions of yvp110 during operation -1 – Yokogawa YVP110 User Manual

Page 63: Block modes -1

Advertising
background image

<10. Actions of YVP110 During Operation>

10-1

IM 21B04C01-01E

10. Actions of YVP110 During Operation

10.1 Block Modes

All function blocks have modes. All blocks have

their mode, expressed by MODE_BLK parameter.

It is a structure of four components; Target,

Actual, Permitted and Normal. Target is the mode

into which an operator wants to bring this block.

This component is writable. Actual shows the

actual mode of the block and is read-only. When

necessary condition is satisfied, actual mode

becomes same to target. There is a chance that

actual mode says different from target by some

reason. Permitted mode shows which mode is

allowed in this Function Block. Normal mode is a

memo for operator to record mode that an operator

expects in normal conditions.
The table below shows the modes supported by

each function block contained in a YVP110.

Table 10.1

Block Modes

Function Block

Modes

Resource

Auto, O/S

Transducer

Auto, O/S

AO

RCas, Cas, Auto, Man, (LO), (IMan),

O/S

DI

Auto, Man, O/S

OS

Auto, Cas, (IMan), O/S

PID

Rout, RCas, Cas, Auto, Man, (LO),

(IMan), O/S

IS

Auto, Man, O/S

AR

Auto, Man, O/S

Modes marked with ( ) in the above table cannot be

specified as “target”.
The following are outlines of each mode.

O/S mode
Means Out of Service mode, in which the block

does not run, and its output and setpoint maintain

their previous values.

IMan mode
Means Initialization Manual mode. Only the AO and

PID blocks in the YVP110 support this mode. When

one of these blocks detects a loss of a correct

path to the downstream block (such as when the

downstream block is in the O/S, Man, Auto or LO

mode), it enters IMan mode. For example, when

the data status of BKCAL_IN in a PID block is “bad”

or “good: not invited”, the PID block enters IMan

mode.

LO mode
Means Local Override mode. If the PID block

enters LO mode, the block output follows the

tracking value (TRK_VAL). In AO block, the block

enters LO mode when the block detects the fault

status. In this case, the block holds the output or

outputs the pre-configured value (FSTATE_VALUE)

according to the setting of options.

Man mode
Means Manual mode. If the data status of a

function block’s input is bad or its target mode is

Man, the block enters Man mode. In Man mode,

the function block does not update its OUT value.

If the target is also Man, it allows the user to write a

desired value to it.

Auto mode
In Auto mode, the function block performs the

specified calculations based on the setpoint

and outputs the result, independently without

interlocking with another function block. The user

can write the setpoint of a function block in this

mode if the target is Auto. If the target mode of

a function block is Auto, or if both of the following

conditions are met for a function bock, the block

enters Auto mode:

• The target mode is Cas or RCas.

• There is an error in communication with the

upstream function block.

Cas mode
Means Cascade mode. In Cas mode, the function

block performs the specified calculations based on

the setpoint that is input from a different function

block via the cascade input parameter and outputs

the result.

ROut mode
Means Remote Output mode. In ROut mode, the

output of the function block is set to the value of the

remote output parameter that is written by a host

computer or others. To prevent a sudden change in

output, the block’s calculations are initialized when

a change in mode occurs.

Advertising