<10. Actions of YVP110 During Operation>

10-2

IM 21B04C01-01E

RCas mode
Means Remote Cascade mode. In RCas

mode, the function block performs the specified

calculations based on the setpoint that is input from

host computer or others via the remote cascade

parameter, and outputs the result.

Table 10.2

Examples of Block Mode Combinations

and Operation Statuses

Operation Statuses AI

PID

AO TB

Transducer Initial

setup, valve setup

(when carrying out

auto tuning, travel

calibration, etc.)

O/S O/S

Modification of

parameter settings

in transducer block

(modification of

control parameter

settings, etc.)

O/S O/S

Constant valve

position control

Auto Auto

PID single-loop

control

Auto

Auto

Cas Auto

PID cascade-loop

control

Auto Primary PID:

Auto

Secondary PID:

Cas

Cas Auto

Table 10.2 shows examples of block mode

combinations in a YVP110 (however, it does not

show all patterns). When a block changes mode

or the data status of a signal changes for some

reason, the other blocks connected to that block

identify the change by detecting the change in

status of an input signal, and change their modes,

too. For example, when the data status of BKCAL_

IN in a PID block changes to bad, the PID block

automatically change mode to IMan to initialize the

control of its downstream block.
The respective modes to which each block should

enter upon occurrence of a communication error

and at a restart, and the handling of signals in

each mode may be defined in the block’s option

parameters such as IO_OPTS and STATUS_

OPTS. For details, see the detailed descriptions of

each function block.

10.2 Alarm Generation

When the YVP110 detects an abnormality in the

device itself by the self-diagnostic function, a device

alarm is issued from the resource or transducer

block. An abnormality in a function block or in a

process value is issued from the corresponding

block as a block error or process alarm.
A YVP110 can report the following alarms and

events.
Analog alerts: A type of alarm generated when

a process value or a deviation value exceeds a

specified limit in the following blocks:

PID block : HI, HI_HI, LO, LO_LO, DV_HI, DV_LO

Discrete alerts: A type of alarm generated when

an abnormal status is detected. For the resource

block, a discrete alert is generated as a block alarm

or write-error alarm. For the DI block, a discrete

alert is generated as a block alarm or DISC alarm.

For the Transducer block, AO, OS, IS, AR block and

PID block, a discrete alert is only generated as a

block alarm.
Update alerts: Generated whenever a change is

made to the settings of the certain parameters.
Table 10.3 shows the elements composing an alert

object.