<8. About Fieldbus>

8-2

IM 21B04C01-01E

• Power supply:

Fieldbus requires a dedicated power supply. It

is recommended that current capacity be well

over the total value of the maximum current

consumed by all devices (including the host).

Conventional DC current cannot be used as is.

• Terminator:

Fieldbus requires two terminators. Refer to

the supplier for details of terminators that are

attached to the host.

• Field devices:

Connect the field devices necessary for

instrumentation. YVP110 has passed the

interoperability test conducted by The Fieldbus

Foundation. In order to properly start Fieldbus,

it is recommended that the devices used satisfy

the requirements of the above test.

• Host:

Used for accessing field devices. A

dedicated host (such as DCS) is used for

an instrumentation line while dedicated

communication tools are used for experimental

purposes.

• Cable:

Used for connecting devices. Refer to “Fieldbus

Technical Information” (TI 38K3A01-01E) for

details of instrumentation cabling. Provide a

cable sufficiently long to connect all devices.

For field branch cabling, use terminal boards

or a connection box as required. If the total

length of the cable is in a range of 2 to 3 meters

for laboratory or other experimental use, the

following simplified cable (a twisted pair wire

with a cross section of 0.9 mm

2

or more (AWG

#18) and cycle period of within 5 cm (2 inches)

may be used. Termination processing depends

on the type of device being deployed. For

YVP110, use an M4 screw terminal claw. Some

hosts require a connector.

Refer to Yokogawa when making arrangements to

purchase the recommended equipment.
The number of devices that can be connected to

a single bus and the cable length vary depending

on system design. When constructing systems,

both the basic and overall design must be carefully

considered to allow device performance to be fully

exhibited.

8.4.1 Connection of Devices

Connect the devices as shown in Figure 9.1.

Connect the terminators at both ends of the

trunk, with a minimum length of the spur laid for

connection.
The polarity of signal and power must be

maintained.

YVP110

Fieldbus power

supply

Terminator

Terminator

HOST

F0802.ai

Figure 8.2

Cabling

Before using a Fieldbus configuration tool other

than the existing host, confirm it does not affect the

loop functionality in which all devices are already

installed in operation. Disconnect the relevant

control loop from the bus if necessary.

8.5 Integration of DD

If the host supports DD (Device Description), the

DD of the YVP110 needs to be installed. Check if

host has the following directory under its default DD

directory.
594543/0001

594543/0007 (/EE)

(594543 is the manufacturer number of

Yokogawa Electric Corporation, and 0001

or 0007 is the YVP110 device number,

respectively.)

If this directory is not found, DD of YVP110 has not

been included. Create the above directory and copy

the DD file (0m0n.ffo,0m0n.sym) (m, n is a numeral)

into the directory.
Once the DD is installed in the directory, the name

and attribute of all parameters of the YVP110 are

displayed.
Off-line configuration is allowed by using the

capability file (CFF). If you do not have the DD or

capability file for the YVP110, you can download it

from www.yokogawa.com/fld/

IMPORTANT

For offline configuration, use the CFF which

matches the specification of the instrument to be

configured. For YVP110, there are three types

of CFF file; one for standard type instruments,

second for the instruments with one or two PID

function blocks are available and the other can

be selected between former two types using

capability level description. Using unmatched

CFF will cause an error upon downloads, etc.