Yokogawa YVP110 User Manual

Page 116

Advertising
background image

<Appendix 1. Function Block Parameters>

A-5

IM 21B04C01-01E

Relative

Index Index

Parameter Name

Default

(factory setting)

Write

Description [Setting range]

33

2033 POSITION_CHAR_

TYPE

1

O/S

Defines the valve position-to-flow characteristics:

1 = linear

2 = equal % (50:1)

3 = equal % (30:1)

4 = quick open (inverse of 50:1 equal %)

5 = Camflex Percentage

255 = user-defined 10-segment function

34

2034 POSITION_CHAR

10, 20, 30, 40,

50, 60, 70, 80,

90

O/S

Defines the coordinates of the segment function

when 255 is set for POSITION_CHAR_TYPE.

[0 to 100, only simple decreasing can be allowed]

35

2035 LIMSW_HI_LIM

+110%

Setting of high limit switch

36

2036 LIMSW_LO_LIM

-10%

Setting of low limit switch

37

2037 ELECT_TEMP

Indicates the temperature on amplifier board

38

2038 TEMPERATURE_

UNIT

1001(degC)

O/S

Defines the unit of temperature indication above:

1001 = degC

1002 = degF

39

2039 SUPPLY_

PRESSURE

140kPa

O/S

Air supply pressure (irrespective of control)

40

2040 SPRING_RANGE

20kPa, 100kPa O/S

Defines the pressure range and unit for valve

operation (with no direct effect on control).

The unit defined here also applies to OUT_

PRESSURE.

1133 = kPa

1137 = bar

1141 = psi

1145 = kgf/cm

2

41

2041 OUT_PRESSURE

Output pressure to valve actuator

42

2042 SERVO_OUTPUT_

SIGNAL

Output current (%) to I/P module

43

2043 SERVO_RATE_GAIN

(*1)

5

O/S

Derivative gain; a control parameter set by auto

tuning [ 2 to 20 ]

44

2044 SERVO_DEADBAND

(*1)

0.5%

O/S

Derivative action dead band; a control parameter

set by auto tuning [0 to 50%]

45

2045 SERVO_OFFSET

(*1)

55% of MV

O/S

Derivative action offset; a control parameter set by

auto tuning [0 to 100 % of MV]

46

2046 BOOST_ON_

THRESHOLD (*1)

1.9, 2.9%

O/S

Threshold for switching on boost action; a control

parameter set by auto tuning [0, 0.1 to 10 %]

47

2047 BOOST_OFF_

THRESHOLD (*1)

1.0, 1.0%

O/S

Threshold for switching off boost action; a control

parameter set by auto tuning [ 0.1 to 10%]

48

2048 BOOST_VALUE (*1) 8, 10% of MV

O/S

Boost value; a control parameter set by auto

tuning [ 0 to 50 % of MV]

49

2049 SERVO_I_SLEEP_

LMT (*1)

0 sec

O/S

Integral-action sleep timer setting; a control

parameter set by auto tuning [ 0 to10 sec]

50

2050 SERVO_P_ALPHA

(*1)

0 %

O/S

Multiplication coefficient for the square of

proportional factor; a control parameter set by

auto tuning [ 0 to 100%]

51

2051 INTERNAL_GAIN

(*1)(*2)

5 rad./mA

O/S

Gain for internal computation; a control parameter

set by auto tuning and travel calibration [ 0.5 to 50

rad./mA]

52

2052 MEAS_GAIN

0 rad./mA

Measurement gain of I/P module, control relay

and valve; a parameter set by auto tuning

53

2053 VALVE_TC

0 sec

Proportional factor of response speed of valve; a

parameter set by auto tuning

54

2054 VALVE_HYS

0 %

Hysteresis of valve actions (%); a parameter set

by auto tuning

55

2055 VALVE_SLIP_WIDTH 0 %

Slip width of valve actions (%); a parameter set by

auto tuning

56

2056 MEAS_PRESS_AIR 0kPa

Air pressure (%); a parameter set by auto tuning

(Valid when an optional pressure sensor is

specified.)

Advertising