<Appendix 6. Manual Tuning Guideline>

A-40

IM 21B04C01-01E

• If necessary, increment the value for SERVO_

RESET by 5.

• The same boost value is set on both the air

delivery and exhaust sides by Auto Tuning. If

the overshoot on the exhaust side is larger than

that on the air delivery side for a double-acting

model, input a negative value in X_BOOST_

VALUE [1] [2], without changing the value of

0 in X_BST_ON_THRESHOLD [1] [2] and

X_BST_OFF_THRESHOLD [1] [2]. First, try to

input a negative value of half that of BOOST_

VALUE [1] [2], and if necessary, increment or

decrement the value by 1.

(3) Improving the stabilization time and slow

overshoot

Decrease the value for SERVO_RESET to improve

the capability of tracking the target value. However,

if the value is too small, the hunting operation or

limit cycle may occur. Verify the 10% step response

and decrement the value by 2 to 3.

(4) Improving the response time

• Increment or decrement the value for BOOST_

VALUE [1] [2] and X_BOOST_VALUE [1] [2] by

2, respectively.

• If necessary, increment the value for SERVO_

GAIN by 30.

(5) Checking hunting operation
Input a value in a large step of approx. 80% to

ensure the hunting operation does not occur. If the

hunting operaion does occur, decrease the value for

SERVO_GAIN to 2/3 or 1/2 of the originally entered

value. Then, increase the value for SERVO_

RESET by approx. 1.5 times.

(6) After tuning the control parameters,

re-check each parameter if necessary.

A6.3 Examples of Tuning Control Parameters

The following table shows examples of tuning parameters for double-acting actuators.
[1] Valtek25sq.in. double-acting actuator, stroke = 0.75 in, capacity = approx. 300 cc,

supply pressure = 400 kPa, hysteresis = 150N

[2] Valtek25sq.in. double-acting actuator, stroke = 0.75 in, capacity = approx. 300 cc,

supply pressure = 400 kPa, hysteresis = 380N

[3] Valtek50sq.in. double-acting actuator, stroke = 2.5 in, capacity = approx. 2000 cc,

supply pressure = 400 kPa, hysteresis = 300N

[4] Valtek50sq.in. double-acting actuator, stroke = 2.5 in, capacity = approx. 2000 cc,

supply pressure = 400 kPa, hysteresis = 1200N

Parameter Name

(Figures in parentheses represent default

values (factory settings))

Valtek25sq.in. Stroke = 0.75 in.

Valtek50sq.in. Stroke = 2.5 in.

Hysteresis =

150N

Hysteresis =

380N

Hysteresis =

300N

Hysteresis =

1200N

SERVO_GAIN (120)

140

120

350

300

SERVO_RESET (15)

8

8

9

24

SERVO_RATE (0.22)

0.4

0.4

0.6

0.5

SERVO_RATE_GAIN (5.0)

10.0

10.0

5.0

5.0

SERVO_DEADBAND (0.0)

0.0

0.0

0.0

0.0

SERVO_OFFSET (55.0)

(55.0) Default

(55.0) Default

(55.0) Default

(55.0) Default

BOOST_ON_THRESHOLD[1][2] (1.9, 2.9)

0.9, 1.9

0.9, 1.9

0.9, 5.1

0.9, 1.9

BOOST_OFF_THRESHOLD[1][2] (1.0, 1.0)

0.5, 0.5

0.5, 0.5

0.5, 0.5

0.5, 0.5

BOOST_VALUE[1][2] (8.0, 10.0)

8.0, 10.0

8.0, 10.0

6.0, 10.0

6.0, 8.0

SERVO_I_SLEEP_LMT (0.0)

1.4

1.4

1.8

1.7

SERVO_P_ALPHA (0.0)

0.0

0.0

0.0

0.0

INTERNAL_GAIN (5.0)

6.8

6.8

14.1

14.1

X_BST_ON_THRESHOLD[1][2] (0.0, 0.0)

0.0, 0.0

0.0, 0.0

0.0, 0.0

0.0, 0.0

X_BST_OFF_THRESHOLD[1][2](0.0, 0.0)

0.0, 0.0

0.0, 0.0

0.0, 0.0

0.0, 0.0

X_BOOST_VALUE[1][2] (0.0, 0.0)

-4.0, -5.0

-8.0, -10.0

-3.0, -6.0

-3.0, -4.0

The above adjusted values are only for reference. Adjust parameters depending on the individual valve, actuator, and operating conditions.

X_BST_ON_THRESHOLD, X_BST_OFF_THRESHOLD, and X_BOOST_VALUE are parameters that are only valid for double-acting