<Appendix 3. DD Methods and DD Menu>

A-27

IM 21B04C01-01E

5) Travel Calibration
This method guides you through each step to

carry out travel calibration. See the respective

descriptions in Section 5.3, “Carrying out Auto

Tuning.”
Travel calibration procedure

• AO/Transducer block mode check

• Execute travel calibration

0% calibration:

Adjustment of FINAL_VALUE (by moving

the valve position to the desired 0%

position)

Execute 0% calibration:

TRAVEL_CALIB_EXEC

Span calibration:

Adjustment of FINAL_VALUE (by moving

the valve position to the desired 100%

position)

Execute span calibration:

TRAVEL_CALIB_EXEC

50% calibration:

Adjustment of FINAL_VALUE (by moving

the valve position to the desired 50%

position)

Execute 50% calibration:

TRAVEL_CALIB_EXEC

Exit

6) Operational Parameter Configuration
This method guides you through the setting of

individual operational parameters excluding the

selection of position-to-flow rate characteristic type.
Operational parameter configuration procedure

• AO/Transducer block mode check

• Operational parameter configuration

Position Limit setting:

FINAL_VALUE_CUTOFF_LO

FINAL_VALUE_CUTOFF_HI

FINAL_VALUE_RANGE

Limit Switch setting:

LIM_SW_LO_LIM

LIM_SW_HI_LIM

Fault Control:

DEVIATION_LIM

DEVIATION_TIME_TH(1)

DEVIATION_TIME_TH(2)

Others:

NEAR_CLOSE_THRESHOLD

Exit

7) Release Fail Safe
This is a method for releasing the device latched by

the fail-safe actions, restoring it to the normal state.
Procedure of releasing fail safe

• Check whether the device is in the latched

state.

• Write “Clear-latched” to parameter RELEASE_

FAIL_SAFE if the device is in the latched state,

to release it from the latched state.

8) Instant Trouble Shooting
This is a help utility which provides troubleshooting

instructions such as indicating the points and

parameters to be checked for troubleshooting.

This method does not contain a utility to change

parameter settings. For troubleshooting of device

statuses, see Chapter 18, “Troubleshooting.”
Instant troubleshooting procedure

• Commanded to check DEVICE_STATUS in the

resource block

• Check XD_ERROR and the remedy will be

displayed if an error has been detected

• Check RELEASE_FAIL_SAFE

• Commanded to check the mechanical linkage,

piping, and installation conditions

• Commanded to check the correct operation of

the device hardware

9) Self Check Execution
The self-check measures the valve’s characteristics

in the same fashion as in auto tuning, and makes

no changes to parameter settings.
Self Check Execution procedure

• AO/TB block mode check

• Self check execution: AUTO_TUNE_EXEC

10) Signature Execution
This method guides you through each step to

perform signature measurement (see Chapter

17, “Diagnostics”). Signature measurement

entails off-line diagnostics functions to measure

characteristics of the valve and positioner.

Comparing the current signature data with the

previously measured data gives clues to identify

the deterioration status and a possible need of

maintenance.