Is function block, 1 is function block schematic, Is function block -1 – Yokogawa YVP110 User Manual

Page 87: Is function block schematic -1

Advertising
background image

<17. IS Function Block>

17-1

IM 21B04C01-01E

17. IS Function Block

The function of the Input Selector (IS) block is to automatically select one signal from multiple input signals

using a specified selection method.
The IS block is used for selective control in which one measured quantity is selected from multiple measured

quantities to be transmitted to the controller as a controlled variable. This feature is primarily used for

temperature control systems.

17.1 IS Function Block Schematic

The following shows the Input Selector function block schematic.

IN_1

Configuration

Auto

Man

MODE

SELECTED

OUT

STATUS_OPTS

SELECT_TYPE

MIN_Good

IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8

DISABLE_1
DISABLE_2
DISABLE_3
DISABLE_4
DISABLE_5
DISABLE_6
DISABLE_7
DISABLE_8

OP_SELECT

F1701.ai

SELECTION

First Good

MINIMUM

MAXIMUM

MIDDLE

Latched Good

AVERAGE

Figure 17.1 IS Block

Input Parameters (Input Terms)
IN_1

: Block input 1

IN_2

: Block input 2

IN_3

: Block input 3

IN_4

: Block input 4

IN_5

: Block input 5

IN_6

: Block input 6

IN_7

: Block input 7

IN_8

: Block input 8

DISABLE_1 : Selector switch 1 to disable input 1 from being selected

DISABLE_2 : Selector switch 2 to disable input 2 from being selected

DISABLE_3 : Selector switch 3 to disable input 3 from being selected

DISABLE_4 : Selector switch 4 to disable input 4 from being selected

DISABLE_5 : Selector switch 5 to disable input 5 from being selected

DISABLE_6 : Selector switch 6 to disable input 6 from being selected

DISABLE_7 : Selector switch 7 to disable input 7 from being selected

DISABLE_8 : Selector switch 8 to disable input 8 from being selected

OP_SELECT : A parameter which can be set by an operator to forcibly employ the input of the selected