Yokogawa YVP110 User Manual

Page 43

Advertising
background image

<7. Standard Specifications>

7-2

IM 21B04C01-01E

Span Adjustment Range:

Within 300% of span

Valve-stem Travel Range:

Linear Motion:

10 to 100 mm (0.4 to 4.0 inch)

(Rotation Range: ±10 to ±25 deg)

Rotary Motion:

20 to 90 deg

Air Consumption and Output Capacity:

Diaphragm, Single Acting Cylinder

Maximum Air

Consumption

0.20 SCFM (0.32 Nm

3

/h) at 140 kPa

Maximum Output

Capacity

4.1 SCFM (6.6 Nm

3

/h) at 140 kPa

Double Acting Cylinder

Maximum Air

Consumption

0.62 SCFM (1.0 Nm

3

/h) at 400 kPa

Maximum Output

Capacity

8.5 SCFM (13.7 Nm

3

/h) at 400 kPa

Ambient Temperature Limits:

Single Acting Actuator:

–40 to 85°C (–40 to 185°F)

Double Acting Actuator:

–40 to 60°C (–40 to 140°F) for standard

–10 to 85°C (14 to 185°F) for high

temperature use with option code /HT

Ambient Humidity Limits:

5 to 95% RH at 40°C (104°F)

EMC Conformity Standards:

,

EN61326-1 Class A, Table 2 (For use in

industrial locations)

Degrees of Protection:

IP65, NEMA4X

Connections:

Air Connection: Rc 1/4 or 1/4 NPT female

Electrical Connection: G 1/2, 1/2 NPT, M20 and

Pg13.5 female

Pressure Gauge Connection:

Pressure

gauge

connection

With pressure

gauge

(Optional)

Connections

Codes

1,5

and

6

Rc 1/8 female /GP, /GM, and /GB

3

1/8 NPT

female

/GE

Mounting:

Front of Actuator with bracket.

Direct Connection for rotary valve.

Weight:

Single Acting Actuator: 2.4 kg (5.3 lb)

Double Acting Actuator: 2.8 kg (6.2 lb)

Performance Specifications

Linearity:

Single Acting Actuator:

±0.5% of Span (including linkages)

Double Acting Actuator:

±1.0% of Span (including linkages)

Hysteresis:

Single Acting Actuator: 0.3% of Span

Double Acting Actuator: 0.5% of Span

Ambient Temperature Effect:

±0.08% of Span/°C

Position Effect:

±0.3% of Span/90 deg

Vibration Effect:

±2% of Span at 2G (15 to 2000 Hz)

Advertising