<Appendix 4. Software Download>

A-31

IM 21B04C01-01E

CAUTION

Carrying out a software download leaves the

PD tag, node address, and transducer block

calibration parameters that are retained in the

nonvolatile memory inside the target device,

but may reset other parameters to the defaults

(except a minor update that does not change

the number of parameters). Hence, where

necessary, save the parameters using an

engineering tool, parameter setting utility, or the

like before carrying out a software download,

and then reconfigure the field device(s) after the

download. For details, see Section A4.6.

CAUTION

The current dissipation of the target field

device increases transitorily immediately after

a download due to erasing of the FlashROM’s

contents. Use a fieldbus power supply which

has sufficient capacity to cover such increases in

feed current.

CAUTION

Upon completion of the activation, the target

fieldbus device performs resetting internally,

which temporarily halts fieldbus communication

and function block executions. Be especially

careful about a valve positioner; the output air

pressure will fall to the minimum level (i.e., zero).

CAUTION

Do not turn off the power to a field device or

disconnect the download tool during a download

or activation. The device may fail as a result.

NOTE

Be careful about the noise on the fieldbus link. If

the fieldbus is noisy, the downloading may take a

very long time or fail.

A4.5 Download Files

Download files have the following filenames (with

the filename extension of “.ffd”). Take care to

choose the correct download file for the target field

device:

“594543” + device family + “_” + device type +

“_” + domain name + “_” + software name + “_”

+ software revision + “.ffd”

For example, the name of the download file for an

YVP may have the following name:

594543000C_0007_YVP_ORIGINAL_R101.ffd

Refer to A4.10(3) DOMAIN_HEADER about each

keyword of the file name.
The device type is “0007” for an YVP transmitter .
The software name is “ORIGINAL” or “UPDATE.”

The former indicates an original file and the latter

an update file. Whenever performing a download

to update the device revision, obtain the original file.

In general, an addition to the parameters or blocks

requires a device revision update.

A4.6 Steps after Activating a

Field Device

When the communication with a field device has

recovered after activating the device, check using

the download tool that the software revision of the

field device has been updated accordingly. The

value of SOFT_REV of the resource block indicates

the software revision.
The PD tag, node address, and transducer block

calibration parameters that are retained in the

nonvolatile memory inside the target device will

remain unchanged after a software download.

However, after a software update which causes an

addition to the block parameters or blocks, or to the

system/network management VFD parameters,

some parameters may be reset to the defaults, thus

requiring parameter setup and engineering again.

For details, see the table below.
Also note that a change in the number of

parameters or blocks requires the DD and

capabilities files corresponding to the new software

revision.