<Appendix 1. Function Block Parameters>

A-13

IM 21B04C01-01E

Relative

Index Index

Parameter

Name

Default

(factory setting)

Write

Description

33

8033 ROUT_IN

Remote control output value set from a computer, etc.

34

8034 SHED_OPT

1

Defines the mode shedding actions, namely, the

changes to be made to MODE.BLK.target and MODE.

BLK.actual when (1) the value of RCAS_IN.status

becomes Bad if MODE_BLK.actual = RCAS, or when (2)

the value of ROUT_IN.status becomes Bad if MODE_

BLK.actual = ROUT.

35

8035 RCAS_OUT

Remote setpoint sent to a host computer, etc.

36

8036 ROUT_OUT

Remote control output value

37

8037 TRK_SCALE 0-100%

Man

Upper and lower scale limits used to convert the output

tracking value (TRK_VAL) to non-dimensional.

38

8038 TRK_IN_D

Switch for output tracking

39

8039 TRK_VAL

Output tracking value. When MODE_BLK.actual = LO,

the value scaled from the TRK_VAL value is set in OUT.

40

8040 FF_VAL

Feed-forward input value. The FF_VAL value is scaled to

a value with the same scale as for OUT, multiplied by the

FF_GAIN value, and then added to the output of the PID

computation.

41

8041 FF_SCALE

0-100%

Man

Scale limits used for converting the FF_VAL value to a

non-dimensional value

42

8042 FF_GAIN

0

Man

Gain for FF_VAL

43

8043 UPDATE_

EVT

Shows the contents of an update event upon

occurrence.

44

8044 BLOCK_ALM —

Shows the contents of a block alarm upon occurrence.

45

8045 ALARM_SUM Enable

Shows the alarm summary (current alarm statuses,

acknowledged/unacknowledged states, masking states)

46

8046 ACK_OPTION 0xFFFF

Selects whether or not the alarms related to the DI block

are automatically self-acknowledged.

47

8047 ALARM_HYS 0.5%

Hysteresis for alarm detection and resetting to prevent

each alarm from occurring and recovering repeatedly

within a short time

48

8048 HI_HI_PRI

0

Priority order of HI_HI_ALM alarm

49

8049 HI_HI_LIM

+INF

Setting for HI_HI_ALM alarm

50

8050 HI_PRI

0

Priority order of HI_ALM alarm

51

8051 HI_LIM

+INF

Setting for HI_ALM alarm

52

8052 LO_PRI

0

Priority order of LO_ALM alarm

53

8053 LO_LIM

+INF

Setting for LO_ALM alarm

54

8054 LO_LO_PRI

0

Priority order of LO_LO_ALM alarm

55

8055 LO_LO_LIM

+INF

Setting for LO_LO_ALM alarm

56

8056 DV_HI_PRI

0

Priority order of DV_HI_ALM alarm

57

8057 DV_HI_LIM

+INF

Setting for DV_HI_ALM alarm

58

8058 DV_LO_PRI

0

Priority order of DV_LO_ALM alarm

59

8059 DV_LO_LIM

+INF

Setting for DV_LO_ALM alarm

60

8060 HI_HI_ALM

Alarm that is generated when the PV value has

exceeded the HI_HI_LIM value and whose priority order*

is defined in HI_HI_PRI.

* Priority order: Only one alarm is generated at a time. When

two or more alarms occur at the same time, the alarm having

the highest priority order is generated. When the PV value

has decreased below [HI_HI_LIM - ALM_HYS], HI_HI_ALM

is reset.

61

8061 HI_ALM

As above

62

8062 LO_ALM

As above Reset when the PV value has increased above

[LO_LIM + ALM_HYS].

63

8063 LO_LO_ALM —

As above

64

8064 DV_HI_ALM

An alarm that is generated when the value of [PV - SP]

has exceeded the DV_HI_LIM value. Other features are

the same as HI_HI_ALM.

65

8065 DV_LO_ALM —

Alarm that is generated when the value of [PV - SP] has

decreased below the DV_LO_LIM value. Other features

are the same as LO_LO_ALM.