<3. Installing YVP110 on Actuator>

3-1

IM 21B04C01-01E

3. Installing YVP110 on Actuator

3.1 General

For installation of a YVP110, see Section 1.4,

“Choosing the Installation Location.” For the

ambient, environmental conditions required

for installation, see Chapter 7, “General

Specifications.”

WARNING

To avoid injury or the process being affected

when installing or replacing a positioner on a

control valve, ensure that:

• All inputs to the valve actuator and other

accessories of the valve and actuator,

including the air supply and electric signal,

are cut off.

• The process has been shut down or the

control valve is isolated from the process by

using bypass valves or the like.

• No pressure remains in the valve actuator.

3.2 Installing YVP110 on

Actuator

A YVP110 can be installed on a valve actuator with

a mounting bracket. Prepare the bracket and clamp

which are necessary to install the valve, according

to the valve. In general, the installation method is

determined by the combination of the control valve

and positioner as well as by the valve manufacturer

who performs the adjustment. For details, consult

the control valve manufacturer.
Required Tools: To install a YVP110, you need to

prepare:

• Nominal 13-mm open end or box end wrench

for M8 bolts used to fix the mounting bracket to

the positioner.

• Nominal 10-mm open end or box end wrench

for M6 bolt used to fix the feedback lever to the

shaft.

3.2.1 Installing YVP110 on Linear-motion

Control Valve

The following shows the general installation

procedure when assembling a YVP110 with a

linear-motion control valve (e.g., a globe valve)

combined with a diaphragm actuator or cylinder

actuator. Note that the most suitable procedure

may differ depending on the shapes of the bracket

and valve actuator, and the structure of the

mounting position.

F0301.ai

Figure 3.1

YVP Installed on Linear-motion Valve/

Actuator

(1) Fixing Bracket to YVP110

Use the four M8 bolts that come with the

YVP110 to tightly fix the mounting bracket to

the YVP110. (See “Part Names” on page 2.1)

The installation method is determined by the

combination of the control valve and positioner

as well as by the valve manufacturer who

performs the adjustment. For details, consult

the control valve manufacturer.