3 definition of combining function blocks, Definition of combining function blocks -2 – Yokogawa YVP110 User Manual

Page 52

Advertising
background image

<9. Configuration>

9-2

IM 21B04C01-01E

Table 9.1

Parameters for Setting Address Range

Symbol

Parameters

Description

V (FUN) First-Unpolled-

Node

Indicates the address

next to the address range

used for the host or other

LM device.

V (NUN) Number-of-

consecutive-

Unpolled-Node

Unused address range.

The devices within the address range written

as “Unused” in Figure 9.1 cannot be used on a

Fieldbus. For other address ranges, the range is

periodically checked to identify when a new device

is mounted. Care must be taken not to allow the

address range to become wider, which can lead to

exhaustive consumption of Fieldbus communication

performance.

Bridge device

Not used

0x00

0x0F

0x14

0x13

0x10

0xF7

0xF8

0xFB

0xFC

0xFF

V(FUN)

V(FUN)1V(NUN)

LM device

Unused

V(NUN)

BASIC device

Default address

Portable device address

F0901.ai

Figure 9.1

Available Range of Node Addresses

To ensure stable operation of Fieldbus, determine

the operation parameters and set them to the LM

devices. While the parameters in Table 9.2 are to

be set, the worst-case value of all the devices to

be connected to the same Fieldbus must be used.

Refer to the specification of each device for details.

Table 9.2 lists YVP110 specification values.

Table 9.2

Operation Parameter Values of the

YVP110 to be Set to LM Devices

Symbol Parameters

Description and Settings

V (ST)

Slot-Time

Indicates the time necessary

for immediate reply of the

device. Unit of time is in

octets (256 μs).

Set maximum specification

for all devices. For YVP, set a

value of 4 or greater.

V (MID)

Minimum-

Inter-PDU-

Delay

Minimum value of

communication data

intervals. Unit of time is in

octets (256 μs). Set the

maximum specification for all

devices. For YVP, set a value

of 4 or greater.

V (MRD) Maximum-

Reply-Delay

The worst case time elapsed

until a reply is recorded. The

unit is Slottime; set the value

so that V (MRD) 3V (ST) is

the maximum value of the

specification for all devices.

For YVP, the setting must be

a value of 12 or greater.

9.3 Definition of Combining

Function Blocks

The input/output parameters for function blocks

are combined. Practically, setting is written to the

YVP110 link object with reference to “Block setting”

in Section 9.6 for details.
For the YVP110, in order to minimize the delay in

data transfer between Transducer block and AO

function block, transducer block are designed to

be executed in conjunction with the execution of

AO function block. Therefore, in order to activate

Transducer block, it is necessary that AO function

block is always defined in the schedule.
The combined blocks need to be executed

synchronously with other blocks on the

communications schedule. In this case, change the

YVP110 schedule according to the following table.

Enclosed values in the table are factory-settings.

YVP110 schedule is set as shown in the following.

Change it as necessary.