<19. Diagnostics>

19-1

IM 21B04C01-01E

19. Diagnostics

19.1 Overview

A spotlighted benefit of fieldbus is the capability

of gaining a wealth of information from the field

via field devices. Particularly for a control valve,

it is expected to become possible to determine

the status of valves which have been difficult to

identify without traveling to the field and physically

examining them, to some extent from a distant

control room through the information transmitted

from the valve positioner. The YVP110 features

diagnostics as shown below.

Table 19.1

Diagnostics of YVP110

Category

Diagnostic Details

Access Points

Positioner

status

diagnostics

Self-diagnostics: Detects

positioner hardware

failures, positioner

software setting errors,

and so on.

• XD_ERROR

in Transducer

block

Valve

status

diagnostics

Measures valve

parameters such as the

hysteresis and slip width.

• Transducer

block’s

respective

parameters

that contain

the values

measured

during the

auto tuning

and selfcheck

Integration: Integrates

the travel distance of the

valve stem and counts

the changes in direction

of the valve action (total

cycle count), and raises

an alarm when each

integrated value reaches

a preset threshold.

• Transducer

block’s

respective

parameters

• XD_ERROR

in Transducer

block

Signature measurement

(featured in a model with

option code /BP):

Measures the signatures

of the valve and

positioner.

• ValveNavi

(Model

YVP20S)

For self-diagnostics, see Section 12.6, “Online

Diagnostics.” For valve parameter measurement,

see Section 5.3, “Carrying out Tuning” and Section

A1.2, “Parameters of Transducer Block.” The

following describes the integration and signature

measurement functions.

19.2 Integration Functions

The transducer block in the YVP110 has the

following parameters containing an integrated

operation result quantity.

Table 19.2

YVP110’s Parameters Containing

Integrated Operation Result Quantity

Item

Parameter

(upper: integrated

value; lower:

threshold)

Description

Total

number of

times of

changes

in direction

of valve

actions

TOTAL_

CYCLE_

COUNT
CYCLE_

COUNT_LIM

Incremented by 1 at each

change in the direction of

the valve action.

The dead band can

be set in CYCLE_

DEADBAND.

Total travel

(%)

TOTAL_

TRAVEL
TRAVEL_LIM

Total travel distance

of the stem position,

regardless of the direction

of the travel, represented

as a percentage of the

valve position span (full

stroke).

The dead band can

be set in CYCLE_

DEADBAND.

Total

close time

(hours)

TOTAL_

CLOSE_TIME
CLOSE_TIME_

LIM

Integrated time periods

when the valve position is

equal to or less than the

threshold set in OPEN_

CLOSE_THRESHOLD.

Total

open time

(hours)

TOTAL_OPEN_

TIME
OPEN_TIME_

LIM

Integrated time periods

when the valve position is

larger than the threshold

set in OPEN_CLOSE_

THRESHOLD

Total near

close time

(hours)

TOTAL_NEAR_

CLOSE_TIM
NEAR_

CLOSE_TIME_

LIM

Integrated time periods

when the valve position is

between a shutoff and the

threshold set in NEAR_

CLOSE_THRESHOLD.

Useful to predict

deterioration of valve

body.

Total

number

of times

of servo

output drift

warning.

SERVO_

WARN_

COUNT

Indicates the total number

of times a drift warning

occurred regarding the

output current to the I/P

module.