<5. Setup>

5-1

IM 21B04C01-01E

5. Setup

CAUTION

During the setup especially when autotuning

is being executed, the valve stem may happen

to move suddenly to an unexpected direction.

Before starting the setup, check and confirm that

the process has been shut down or the control

valve is isolated from the process. During the

setup, keep away from the movable parts to

avoid injury.

5.1 General

After mechanically attaching the YVP110 to an

actuator and finishing the wiring and piping, connect

the YVP110 to a fieldbus and make settings, such

as carrying out auto tuning and setting the tight-shut

option, using a parameter setting tool or the like.

IMPORTANT

For the operation of a parameter setting tool,

read the manual of each tool. Also, read the

Chapters 8 through 10 and 12 of this manual

to become familiar with the configuration of

the fieldbus instrument and the function of the

transducer block before starting adjustment.

Check that the piping and wiring connections are

all correct, and then supply the specified input

voltage and air pressure. For the connection to

the fieldbus, see the chapters 4.3 'Wiring' and 8.4

'System Configuration'.
Parameter settings for the actuator and valve are to

be made in the parameters in the transducer block

inside the YVP110 positioner. For details of each

parameter, refer to the parameters list in Appendix

1. Follow the procedure below.

Set basic parameters (Section 5.2)

Carry out tuning (Section 5.3)

Check valve actions (Section 5.4)

Set transducer block's parameters (Section 5.5)

F0501.ai

Figure 5.1

Setup Procedure

5.2 Setting Basic Parameters

First, set the target mode's in the parameters

MODE_BLK of the transducer block and AO

function block to O/S (Out of Service). When either

one or both of the transducer block and AO function

block are in the O/S mode, the transducer block's

parameters that determine the valve actions are

write-locked.
(1) Selecting the Acting Direction of Valve

In the parameter ACT_FAIL_ACTION, set

the value, 1 or 2, corresponding to the acting

direction of the valve, whether the valve opens

or closes due to an increase of the pneumatic

pressure. The setting in ACT_FAIL_ACTION

determines the relationship between the

pneumatic input signal and 0-100% of the

valve position, where the 0% position means

complete closure.
1 = air to open

2 = air to close

IMPORTANT

For the transducer block, the 0% output always

means complete closure of the valve. Set

ACT_FAIL_ACTION correctly in accordance

with the acting direction of the valve used.

Nonetheless, the 0-100% of the transducer

block's output can be logically reversed by setting

IO_OPTS in the AO block to true.
Independently of the above setting, YVP110

always acts identical upon power off and cut-off

of the air supply.

When a power failure or serious hardware

damage is detected, the YVP110 cuts the

current signal being fed to the I/P module to

zero, moving the valve to the safe side. The

action of the YVP110 upon occurrence of a

communication error can be predefined by AO

block’s parameters; see Section 13.3.1, “Fault

State.”