<13. AO Function Block>

13-3

IM 21B04C01-01E

13.6 Mode Shedding upon

Computer Failure

When the data status of RCAS_IN falls to Bad

while the block in question is running in RCas

(remote cascade) mode, mode shedding occurs in

accordance with the setting in SHED_OPT. Table

13.3 shows the available selections for SHED_OPT

setting for the AO block.

Table 13.3

SHED_OPT of AO Block

bit Available Setting

for SHED_OPT

Actions upon Computer

Failure

1 Normal shed,

normal return

Sets MODE_BLK.actual to

Cas*

1

, and leaves MODE_

BLK.target unchanged.

2 Normal shed, no

return

Sets both MODE_BLK.actual

and MODE_BLK.target to

Cas*

1

.

3 Shed to Auto,

normal return

Sets MODE_BLK.actual to

Auto*

2

, and leaves MODE_

BLK.target unchanged.

4 Shed to Auto, no

return

Sets both MODE_BLK.actual

and MODE_BLK.target to

Auto*

2

.

5 Shed to Manual,

normal return

Sets MODE_BLK.actual to

Man, and leaves MODE_

BLK.target unchanged.

6 Shed to Manual,

no return

Sets both MODE_BLK.actual

and MODE_BLK.target to

Man.

7 Shed to retained

target, Normal

return

If Cas is set in MODE_BLK.

target,

- sets MODE_BLK.actual to

Cas and

- leaves MODE_BLK.target

unchanged.

If Cas is not set in MODE_

BLK.target,

- sets MODE_BLK.actual to

Auto*

2

and

- leaves MODE_BLK.target

unchanged.

8 Shed to retained

target, No return

If Cas is set in MODE_BLK.

target, sets:

- MODE_BLK.actual to

Cas, and

- MODE_BLK.target to

Cas, too.

If Cas is not set in MODE_

BLK.target, sets:

- MODE_BLK.actual to

Auto*

2

, and

- MODE_BLK.target to

Cas.

*1:

The modes to which the AO block can transfer are limited

to those set in MODE_BLK.permitted, and the priority

levels of modes are as shown below. In fact, if Normal

shed, normal return is set for SHED_OPT, the detection of

a computer failure causes MODE_BLK.actual to change

to Cas, Auto, or Man, whichever is set in MODE_BLK.

permitted and has the lowest priority level.

Man

Auto

Cas

RCas

ROut

Higher priority level

Lower priority level

*2:

Only when Auto is set as permitted mode.

NOTE: If a control block is connected as a cascade

primary block of the AO block, a mode transition of the

AO block to Cas occurs in the following sequence due to

initialization of the cascade connection: RCas → Auto →

Cas.

13.7 Initialization at Start

To prevent a sudden change in output when the AO

block carries out the specified actions for the first

time after the power is turned on, it:
1) Equalizes SP to PV if the Faultstate Type option

(bit no. 7) in IO_OPTS is false.

2) Equalizes OUT to READBACK.
If the Faultstate Type option (bit no. 7) in IO_OPTS

is true, it restores FSTATE_VAL in SP.

13.8 Alarm Processing

When a condition shown in the table below is met,

the AO block changes the bit statuses of BLOCK_

ERROR accordingly and generates a block alarm.

Table 13.4

BLOCK_ERROR in AO Block

Bit Name of Error

Represented

Condition

3 Simulate Active SIMULATE is active.
4 Local Override

Fault state is on, and

Propagate Fault Backward is

false.

7 Input Failure /

process variable

has BAD status

Propagate Fault Backward in

STATUS_OPTS is false, and

the sub-status component of

the status of READBACK is

sensor failure or device failure.

15 Out-of-Service

The target mode is O/S.