<Appendix 4. Software Download>

A-32

IM 21B04C01-01E

Table A4.1 Actions after Software Update

Contents of Software Update

Action

Does not change the number of parameters.

Re-setup of parameters not needed.

Adds a block parameter.

Setup of the added parameter needed.

Adds a block.

Reengineering and setup of the added block’s parameters needed.

Changes the number of system/network

management VFD parameters

Reengineering needed.

A4.7 Troubleshooting

For information on the download tool’s error messages, see also the software’s User’s Manual.

Table A4.2 Problems after Software Update

Symptom

Cause

Remedy

An error occurs before starting a

download, disabling the download.

The selected download file is not for

the selected field device.

Check SOFTDWN_ERROR in the

resource block and obtain the correct file.

An error occurs after starting a

download, disabling the download.

You attempted to update the device

revision by downloading a file which is

not an original file.

Check SOFTDWN_ERROR in the

resource block and obtain the original file.

The selected field device does not

support software downloading.

Check whether the option code /EE is

included in the model and suffix codes of

the device.

The voltage on the fieldbus segment

falls below the specified limit (9 volts).

Check the capacity of the field bus power

supply used and the voltage at the terminal.

There was an error in a checksum or

the number of transmission bytes.

Check SOFTDWN_ERROR in the

resource block and obtain the correct file.

The download tool does not allow

download with same software revision.

Check the setting of the download tool.

The download takes far longer than

expected or fails frequently.

The fieldbus segment is noisy.

Check the noise level on the fieldbus

segment.

An error occurs after activation.

Transient error caused by the internal

resetting of the field device

Check whether communication with the

field device has recovered after a while.

The new software does not work

after the activation.

The file of the current revision was

downloaded.

Obtain the correct file.

Failure of the memory in field device,

etc.

Check SOFTDWN_ERROR in the

resource block, and re-try downloading.

If fails, place a service call.

A4.8 Resource Block’s Parameters Relating to Software Download

Table A4.3 Additional Parameters of Resource Block

Relative

Index

Index

Parameter Name

Default

(Factory Set)

Write

Mode

Description

53

1053 SOFTDWN_PROTECT

0x01

Defines whether to accept software downloads.

0x01: Unprotected

0x02: Protected

54

1054 SOFTDWN_FORMAT

0x01

Selects the software download method.

0x01: Standard

55

1055 SOFTDWN_COUNT

0

Indicates the number of times the internal

FlashROM was erased.

56

1056 SOFTDWN_ACT_AREA 0

Indicates the ROM number of the currently

working FlashROM.

0: FlashROM #0 working

1: FlashROM #1 working

57

1057 SOFTDWN_MOD_REV

1, 0, 0, 0, 0, 0,

0, 0, 0

Indicates the software module revision.

58

1058 SOFTDWN_ERROR

0

Indicates an error during a software download.

See Table 4.