<Appendix 1. Function Block Parameters>

A-4

IM 21B04C01-01E

Relative

Index Index

Parameter Name

Default

(factory setting)

Write

Description [Setting range]

9

2009 TRANSDUCER_

DIRECTORY

1, 10

Index to the text describing the transducer

contained in the YVP110 positioner

10

2010 TRANSDUCER_

TYPE

106

Transducer type

11

2011 XD_ERROR

0

Stores the error prioritized at the highest level

from among the errors that are currently occurring

in the transducer block.

12

2012 CORRECTION_

DIRCTORY

1, 13

Stores the number of data collection and the index

number to be started with.

13

2013 FINAL_VALUE

O/S

Stores the valve control level and status written by

the AO block.

14

2014 FINAL_VALUE_

RANGE

-10%, 110%

O/S

Defines the upper and lower range limits of

FINAL_VALUE, and the unit code and decimal

point position for value indication of FINAL_

VALUE.

15

2015 FINAL_VALUE_

CUTOFF_HI

110%

O/S

If the value of FINAL_VALUE is greater than the

value set in this parameter, the YVP110 moves

the valve to the full-open position. There is a

hysteresis of 1% at the release time. If the value of

FINAL_VALUE becomes 1% less than the value

set in this parameter, this function is released.

16

2016 FINAL_VALUE_

CUTOFF_LO

0%

O/S

If the value of FINAL_VALUE is less than the

value set in this parameter, the YVP110 moves

the valve to the shut-off position. There is a

hysteresis of 1% at the release time. If the value

of FINAL_VALUE becomes 1% greater than

the value set in this parameter, this function is

released.

17

2017 FINAL_POSITION_

VALUE

Stores the position data read by the valve position

sensor.

18

2018 SERVO_GAIN (*1)

120

O/S

Static control loop gain set by auto tuning [0.5 to

1300 ]

19

2019 SERVO_RESET (*1) 15 sec

O/S

Integral time set by auto tuning

20

2020 SERVO_RATE (*1)

0. 22 sec

O/S

Derivative time set by auto tuning

21

2021 ACT_FAIL_ACTION 1

O/S

Specifies the actuator action direction (in case of

losing of air supply pressure):

1 = Air to Open

2 = Air to Close

22

2022 ACT_MAN_ID

0

ID of actuator manufacturer

23

2023 ACT_MODEL_NUM Null

Model number of actuator

24

2024 ACT_SN

0

Serial number of actuator

25

2025 VALVE_MAN_ID

0

ID of valve manufacturer

26

2026 VALVE_MODEL_

NUM

Null

Model number of valve

27

2027 VALVE_SN

0

Serial number of valve

28

2028 VALVE_TYPE

1

O/S

Valve type:

1 = linear-motion valve

2 = rotary-motion valve

29

2029 XD_CAL_LOC

Null

Shows and is used to record the location where

the positioner was calibrated.

30

2030 XD_CAL_DATE

01/01/00

Shows and is used to record the date when the

positioner was calibrated.

31

2031 XD_CAL_WHO

Null

Shows and is used to record the person who

calibrated the positioner.

32

2032 ALARM_SUM

Shows the alarm summary (current alarm

statuses, acknowledged/unacknowledged states,

masking states) for the transducer block.