3 csa certification, 4 tiis certification, Csa certification -12 – Yokogawa YVP110 User Manual

Page 23: Tiis certification -12, Caution

Advertising
background image

<1. Notes on Handling>

1-12

IM 21B04C01-01E

1.9.3 CSA Certification

A) CSA Explosionproof Type
Cautions for CSA Explosionproof type.
Note 1. Model YVP110 Advanced Valve Positioner

with optional code /CF1 are applicable for

use in hazardous locations:

• Applicable standard: C22.2 No. 0, No. 0.4,

No. 0.5, No. 25, No. 30, No. 94, No. 1010.1

• Certificate: 1186507

• Explosionproof for Class I, Groups B, C and

D; Class II, Groups E, F and G; Class III.

• Enclosure Rating: Type 4X

• Temperature Code: T6 and T5

• Ambient Temperature: –40 to 75°C for T6,

–40 to 82°C for T5

Note 2. Wiring

• All wiring shall comply with National Electrical

Code ANSI/NFPA 70 and Local Electrical

Codes.

• “FACTORY SEALED, CONDUIT SEAL NOT

REQUIRED.”

• When the ambient temperature is 60°C

or more, use an external cable having a

maximum allowable heat-resistance of at

least 90°C.

Note 3. Maintenance and Repair

• The instrument modification or parts

replacement by other than authorized

representative of Yokogawa Electric

Corporation is prohibited and will void CSA

Certification.

1.9.4 TIIS Certification

A) TIIS Flameproof Type
The model YVP110 Valve Positioner with optional

code /JF3, which has obtained certification

according to technical criteria for explosion-

protected construction of electric machinery and

equipment (Standards Notification No. 556 from

the Japanese Ministry of Labor) conforming to IEC

standards, is designed for hazardous areas where

inflammable gases or vapors may be present. (This

allows installation in Division 1 and 2 areas)
To preserve the safety of flameproof equipment

requires great care during mounting, wiring, and

piping. Safety requirements also place restrictions

on maintenance and repair activities. Users

absolutely must read “Installation and Operating

Precautions for JIS Flameproof Equipment” at the

end of this manual.

CAUTION

When selecting cables for TIIS flameproof type

positioners, use cables having a maximum

allowable heat resistance of at least 70°C.

Advertising