<20. Troubleshooting>

20-2

IM 21B04C01-01E

20.4 Troubleshooting Valve Control

Problem

Presumed Cause

Remedy

Ref. Section

A change in setpoint causes

no action of the valve.

Air piping is incorrect.

Correct piping.

4.2

The instrument is in FAILSAFE

state.

Write ‘Clear non-latch’ to RELEASE_

FAILSAFE parameter.

12.6.2

Air supply is not being fed.

Supply proper air pressure

4.2

The valve has failed.

Apply a pneumatic pressure directly

to the valve actuator and check

whether there is valve action.

3.2.3

The I/P module or control relay

has failed, or there is breakage

in the cable between the I/P

module and control relay.

If the output pressure does

not increase even though the

SERVO_OUTPUT_SIGNAL value

is at maximum, contact the nearest

service station or representative

office.

The valve’s full stroke is

insufficient for the setpoint

input.

The air supply pressure is not

high enough to drive the valve

actuator.

Check the air supply pressure rating

for the valve actuator and supply air

at the correct pressure, and write 4

or 2 to AUTO_TUNE_EXEC to redo

autotning.

4.2, 5.3

The range of the setpoint is

limited by software.

Check the values of SP_HI_LIM

and SP_LO_LIM in the AO block

and FINAL_VALUE_RANGE in the

transducer block.

13.3,

Appendix 1

The deviation between

the setpoint and readback

signal remains.

The tight-shut or full-open action

is active.

Check the values of FINAL_VALUE_

CUTOFF_HI and FINAL_VALUE_

CUTOFF_LO.

12.2.4,

Appendix 1

The travel calibration has not

been performed correctly.

Write 2 to AUTO_TUNE_EXEC to

perform 0 &100% point adjustment.

5.3

The valve oscillates

cyclically (limit cycle).

The friction of grand packing is

large.

1) Write 4 or 3 to AUTO_TUNE_

EXEC to redo auto tuning.

5.3

2) Use the actuator of proper size.

The dead band of integral action

is too little.

Write 4 or 3 to AUTO_TUNE_EXEC

to redo auto tuning. Or, increase the

SERVO_DEADBAND setting until

the valve stops oscillating.

5.3, 12.7,

Appendix 1,

Appendix 6

There’s air leak from the pipe

of output pressure, or feedback

lever is not correctly attached.

Check the piping and attachment of

the lever, and write 4 or 3 to AUTO_

TUNE_EXEC to redo autotuning.

Chapter 3,

5.3

Valve responses are too

slow.

If only the responses that require

air suction are slow, it means

that the regulator’s maximum

capacity is large enough.

Replace the regulator.

The I/P module’s nozzle has

become blocked from dirt

contained in the air supply or the

like.

Check whether or not error 114

or 122 occurs in XD_ERROR in

steady states. If it does occur,

contact the nearest service station or

representative office.

12.6.1

The control relay’s nozzle

has become blocked from dirt

contained in the air supply or the

like.

Check whether or not error 114 or

122 occurs in XD_ERROR in steady

states.

12.6.1

The control gain is insufficient.

Write 4 or 3 to AUTO_TUNE_EXEC

to redo auto tuning. Or, increase the

SERVO_GAIN setting.

5.3, 12.7,

Appendix 1,

Appendix 6

There’s air leak from the pipe

of output pressure, or feedback

lever is not correctly attached.

Check the piping and attachment of

the lever, and write 4 or 3 to AUTO_

TUNE_EXEC to redo autotuning.

Chapter 3,

5.3

The pressure balance deviation

is too large.

Adjust the pressure balance of

control relay.

6.3.4