13 initialization and manual fallback (iman), 14 manual fallback, 1 status_opts – Yokogawa YVP110 User Manual

Page 85: 15 auto fallback, 16 mode shedding upon computer failure, 1 status_opts -4

Advertising
background image

<16. PID Function Block>

16-4

IM 21B04C01-01E

16.13 Initialization and Manual

Fallback (IMan)

Initialization and manual fallback denotes a set of

abnormality handling actions in which a PID block

changes mode to IMan (initialization manual) and

suspends the control action. Initialization and

manual fallback takes place only when the following

condition is met:

• The quality component of BKCAL_IN.status

(data status of BKCAL_IN) is Bad.

- OR -

• The quality component of BKCAL_IN.status is

Good (c)

- AND -

The sub-status component of BKCAL_IN.status

is FSA, LO, NI, or IR.

16.14 Manual Fallback

Manual fallback denotes an abnormality handling

action in which a PID block changes mode to Man

(manual) and suspends the control action.
The manual fallback action is enabled to take place

if the Target to Manual if BAD IN option in STATUS_

OPTS is set as true, and it takes place when the

following condition is met:

• IN.status (data status of IN) is Bad except when

the control action bypass is on.

16.14.1 STATUS_OPTS

The table below shows the options in STATUS_

OPTS.

Table 16.4

STATUS_OPTS of PID Block

Bit

Options in

STATUS_

OPTS

Description

0 IFS if BAD IN Sets the sub-status component

of OUT.status to IFS if IN.status

is Bad except when PID control

bypass is on.

1 IFS if BAD

CAS IN

Sets the sub-status component of

OUT.status to IFS if CAS_IN.status

is Bad.

2 Use Uncertain

as Good

Does not regard IN as being in Bad

status when IN.status is Uncertain

(to prevent mode transitions

from being affected when it is

Uncertain).

5 Target to

Manual if BAD

IN

Automatically changes the value of

MODE_BLK.target to Man when IN

falls to Bad status.

9 Target to next

permitted

mode if BAD

CAS IN

Automatically changes the value

of MODE_BLK.target to Auto (or to

Man if Auto is not set in Permitted)

when CAS_IN falls to Bad status.

16.15 Auto Fallback

Auto fallback denotes an action in which a PID

block changes mode from Cas to Auto and

continues automatic PID control with the user-set

setpoint. To enable the auto fallback action to take

place:

• The Target to next permitted mode if BAD CAS

IN option must be preset to true in STATUS_

OPTS.

- AND -

• Auto must be preset in MODE_BLK.permitted.

If the above settings are made, auto fallback

takes place automatically when the following

condition is met:

• CAS_IN.status (data status of cascade

setpoint) is Bad except when the control action

bypass is on.

16.16 Mode Shedding upon

Computer Failure

When (1) the data status of RCAS_IN, which is the

setting received from a computer as the setpoint

SP, falls to Bad while the PID block is running in the

RCas (remote cascade) mode, or when (2) the data

status of ROUT_IN, which is the setting received

from a computer as the remote output signal, falls

to Bad while the PID block is running in the ROut

(remote output) mode; mode shedding occurs in

accordance with the SHED_OPT setting.

Advertising