Yokogawa YVP110 User Manual

Page 19

Advertising
background image

<1. Notes on Handling>

1-8

IM 21B04C01-01E

FISCO Model

Non-hazardous

Locations

Hazardous Locations

F0106.ai

Terminator

(FISCO Model)

Ex i

Field Instruments

(Passive)

Hand-

held-

Terminal

Supply Unit

(FISCO Model)

Terminator

Data

U

U

I

I.S. fieldbus system complying with FISCO

The criterion for such interconnection is that the

voltage (Ui), the current (Ii) and the power (Pi),

which intrinsically safe apparatus can receive,

must be equal or greater than the voltage (Uo),

the current (Io) and the power (Po) which can be

provided by the associated apparatus (supply unit).

In addition, the maximum unprotected residual

capacitance (Ci) and inductance (Li) of each

apparatus (other than the terminators) connected

to the fieldbus line must be equal or less than 5 nF

and 10 µH respectively.
Supply unit
The supply unit must be certified by a notified body

as FISCO model and following trapezoidal output

characteristic is used.
Uo = 14 to 24 V (I.S. maximum value)

Io based on spark test result or other assessment,

ex. 133 mA for Uo = 15 V (Group IIC)
The maximum allowed Co and Lo are determined

by the combinations as specified below.
Cable
The cable used to interconnect the devices needs

to comply with the following parameters:

loop resistance R': 15 to 150 Ω/km

inductance per unit length L': 0.4 to 1 mH/km

capacitance per unit length C': 80 to 200 nF/km

C' = C' line/line + 0.5 C' line/screen, if both lines

are floating

or

C' = C' line/line + C' line/screen, if the screen is

connected to one line

length of spur cable: max. 30 m (Ex ia IIC T4) or

120 m (Ex ia IIB T4)

length of trunk cable: max. 1 km (Ex ia IIC T4)

or 1.9 km (Ex ia IIB T4)

Terminators
The terminator must be certified by a notified body

as FISCO model and at each end of the trunk

cable an approved line terminator with the following

parameters is suitable:

R = 90 to 100 Ω

C = 0 to 2.2 µF

The resistor must be infallible according to EN

50020. One of the two allowed terminators might

already be integrated in the associated apparatus

(bus supply unit).
Number of Devices
The number of devices (max. 32) possible on a

fieldbus link depends on factors such as the power

consumption of each device, the type of cable used,

use of repeaters, etc.

Entity Model

Non-hazardous

Locations

Hazardous Locations

F0107.ai

Terminator

Ex i

Field Instruments

(Passive)

Hand-

held-

Terminal

Supply Unit

Terminator

Data

U

U

I

I.S. fieldbus system complying with Entity model

Advertising