2 position-to-flow rate characteristic conversion, 3 final_value and range, 4 tight-shut and full-open actions – Yokogawa YVP110 User Manual

Page 71: 3 backward path, 1 final_position_value, 2 limit switches, Position-to-flow rate characteristic conversion -2, Final_value and range -2, Tight-shut and full-open actions -2, Backward path -2 12.3.1

Advertising
background image

<12. Transducer Block>

12-2

IM 21B04C01-01E

12.2.2 Position-to-flow Rate

Characteristic Conversion

The parameter POSITION_CHAR_TYPE defines

the characteristics between the valve position and

flow rate, and can be set to one the following:

1 = linear

2 = equal percent (50:1)

3 = equal percent (30:1)

4 = quick open (reversal of equal percent 50:1)

5 = Camflex Percen tage

255 = user-defined

Writing the value 255 allows you to define the

desired characteristics by 10 line segments for

evenly divided input levels. The coordinates

(0,0) and (100,100) are fixed; set the values

corresponding to OUT(Output of AO block) = 10%,

20%, 30%..., 80%, 90%. Note that a set value must

be greater than the preceding set value; the output

must increase as the input increases.
This flow rate conversion is applied to the signal in

the backword path as well.

12.2.3 FINAL_VALUE and Range

The parameter FINAL_VALUE contains the valve

position setpoint for valve control, and its value is

always a percent value where 0% is the shut-off

position as is the case for the input signal. High and

low limits for the value of FINAL_VALUE.value can

be set in FINAL_VALUE_RANGE.

12.2.4 Tight-shut and Full-open Actions

The tight-shut action is an action to decrease the

output pressure to a level much lower than the 0%

pressure level for an air-to-open valve (or increase

it to a level much higher than the 0% pressure level

for an air-to-close valve) when FINAL_VALUE.value

is less than FINAL_VALUE_CUTOFF_LO in order

to ensure that the valve is tightly shut off. After the

tight-shut action is activated, when FINAL_VALUE.

value becomes greater than FINAL_VALUE_

CUTOFF_LO by 1% or more, the tight-shut action

will turn off.
Conversely, the full-open action is an action to

increase the output pressure to a level much higher

than the 100% pressure level for an air-to-open

valve (or decrease it to a level much lower than the

100% pressure level for an air-to-close valve) when

FINAL_VALUE.value is larger than FINAL_VALUE_

CUTOFF_HI in order to ensure that the valve is fully

open. After the full-open action is activated, when

FINAL_VALUE.value becomes less than FINAL_

VALUE_CUTOFF_HI by 1% or more, the full-open

action will turn off.
Although the actual output signal level is changed

to a level outside the range during the period when

the tight-shut or full-open action is on, the value of

FINAL_VALUE.value remains as computed and is

not affected by these actions.

12.3 Backward Path

The following describes the signal input from the

device hardware to the transducer block and then

passed to other function blocks.

12.3.1 FINAL_POSITION_VALUE

The parameter FINAL_POSITION_VALUE contains

a percentage value of the valve position sent from

the position sensor where 0% is the shut-off position

as is the case for FINAL_VALUE.value. When one

or more of the following conditions become true, the

data status of FINAL_POSITION_VALUE becomes

Bad, which is notified to the connected AO block

and upstream function blocks:

• Bad - Out of service: The block is in the O/S

mode.

• Bad - Sensor failure: The position sensor has

failed.

• Bad - Device failure: The A/D converter has

failed.

• Bad - Non specific: The deviation exceeds the

limit.

12.3.2 Limit Switches

Limit switches monitor whether the valve position

has reached a specified high or low limit position

and send the high limit switch status to channel 2

and the low limit switch status to channel 3. The

thresholds (settings) for the high and low limit

switches should be set in LIMSW_HI_LIM and

LIMSW_LO_LIM. The switch statuses sent to

channels 2 and 3 mean:

0 = off (inactive)

1 = on (active)

Hysteresis of 1% is applied for both High and Low

limit switch. While the limit switch of high side stays

ON, it turns to OFF again only when the value

of FINAL_POSITION_VALUE becomes smaller

by 1% or less than the value of LIMSW_HI_LIM.

Also, while limit switch of low side stays ON, it

turns to OFF again only when the value of FINAL_

POSITION_VALUE becomes greater by 1 % or

more than the value of LIMSW_LO_LIM.

Advertising