<Appendix 3. DD Methods and DD Menu>

A-28

IM 21B04C01-01E

Signature execution procedure

• AO/TB block mode check

• Signature measurement execution

Measure all:

Setting all signature measurement

conditions

Executing signature measurement (SIGN_

MEAS_EXEC)

Uploading data (see Item 11) below).

Measure actuator signature:

Setting STD_ACT_SIGN_SET

Executing signature measurement (SIGN_

MEAS_EXEC)

Uploading data (see Item 11) below).

Measure extended actuator signature:

Setting EXT_ACT_SIGN_SET

Executing signature measurement (SIGN_

MEAS_EXEC)

Uploading data (see Item 11) below).

Step response test:

Setting STEP_RESP_SET

Executing step response test (SIGN_

MEAS_EXEC)

Uploading data (see Item 11) below).

Measure positioner signature:

Setting POSITIONER_SIGN_SET

Executing signature measurement (SIGN_

MEAS_EXEC)

Uploading data (see Item 11) below).

Exit

11) Upload Signature Data
This method guides you through uploading the

signature data that has been measured and stored

in the positioner, from selecting the database you

want to upload, to adjusting the data pointer to the

leading position of the desired data and uploading

it.
Signature data uploading procedure

• Select action from menu

Upload data:

Uploading data from SIGN_DATA_X and

SIGN_DATA_Y

Select upload database (meaning, “select

the database to be uploaded”)

Change data pointer

Exit

12) Upload Signature Header Data
This method guides you through uploading the

header data of a signature measurement that has

already been performed. The header data contains

the measurement condition settings, the ambient

temperature at the measurement, the date of the

measurement, and so on. Users can select a

database to access the desired header data.
Signature header data uploading procedure

• Selection of action from menu

Upload header data:

Select upload database (meaning, “select

the database to be uploaded”)

Exit

A3.2.2 AO Block

1) Simulation Enable
This is a method for causing the AO block to

activate the simulation status. When a block is

in the simulation status, you can apply simulated

inputs to the block to let the block function with

that input, and check the actions of the function

block application and alarm processing. Since the

simulation function is disabled to run normally in

consideration of the nature of its functionality, when

using this method, the simulation function needs to

be rendered active by doing either of the following:

• Write “REMOTE LOOP TEST SWITCH” to

SIM_ENABLE_MSG in the resource block.

• Turn on the SIM.ENABLE hardware switch on

the YPV110’s amplifier assembly (see Section

10.3, “Simulation Function”).

Simulation enabling procedure

• Check that the simulation switch is ON (active).

• Check the AO block mode

• Change the value of SIMULATE.status to

“Enable”

• Set the simulated input value in SIMULATE.

value

2) Simulation Disable
This is a method for disabling the simulation

function of the AO block.
Simulation disabling procedure

• Confirm whether the simulation function can be

disabled.

• Change the value of SIMULATE.status to

“Disable”