Yokogawa YVP110 User Manual

Page 117

Advertising
background image

<Appendix 1. Function Block Parameters>

A-6

IM 21B04C01-01E

Relative

Index Index

Parameter Name

Default

(factory setting)

Write

Description [Setting range]

57

2057 MEAS_PRESS_

SUPPLY

0kPa

Air supply pressure (%); a parameter set by auto

tuning (Valid when an optional pressure sensor is

specified.)

58

2058 MEAS_SPRING_

RANGE

0kPa

Spring range of valve; a parameter set by auto

tuning (Valid when an optional pressure sensor is

specified.)

59

2059 CONTROL_DIR

2

Defines the acting direction of the feedback loop:

1 = direct

2 = reverse

60

2060 THETA_HI (*1)(*2)

+ 0.2 rad.

Upper angle signal limit of position sensor (in

radians)

61

2061 THETA_LO (*1)(*2)

-0.2 rad.

Upper angle signal limit of position sensor (in

radians)

62

2062 THETA_P (*1)(*2)

0 rad.

Angle signal equal to 50 % from position sensor

(in radians)

63

2063 TRAVEL_CALIB_

EXEC

1

O/S

Switch for starting a travel calibration.

64

2064 TRAVEL_CALIB_

RESULT

1

Indicates the result of a travel calibration.

65

2065 OPEN_STOP_ADJ

Not used for YVP110.

66

2066 AUTO_TUNE_EXEC 1

O/S

Switch for starting auto tuning.

67

2067 AUTO_TUNE_

RESULT

1

Indicates the result of auto tuning.

68

2068 AUTO_TUNE_STATE 0

Indicates auto tuning sequence number.

69

2069 SERVO_RET_TO_

DFLT

1

O/S

Writing 2 to this parameter resets all control

parameters to the defaults:

1 = off

2 = set (to the defaults)

70

2070 ADVAL_FW

Digital value of valve control signal, setpoint

equivalent to A/D value of valve position signal.

71

2071 ADVAL_BW

A/D value of valve position signal

72

2072 ADVAL_PRESS

A/D value of pressure from sensor

73

2073 ADVAL_T

A/D value of temperature from sensor

74

2074 TOTAL_CYCLE_

COUNT

0

O/S

Total number of cycles. To reset the count, write 0.

75

2075 CYCLE_DEADBAND 0.25%

Dead band of cycle counting

76

2076 CYCLE_COUNT_LIM 2^32-1

High-limit alarm setting for TOTAL_CYCLE_

COUNT. When TOTAL_CYCLE_COUNT has

reached this setting, a block alarm is generated.

77

2077 TOTAL_TRAVEL

0

O/S

Total amount of travel. To reset the count, write 0.

78

2078 TRAVEL_

DEADBAND

0.25%

Dead band of travel integration

79

2079 TRAVEL_LIM

2^32-1

High-limit alarm setting for TOTAL_TRAVEL.

When TOTAL_TRAVEL has reached this setting,

a block alarm is generated.

80

2080 TOTAL_OPEN_TIME 0 hour

Total time other than counted for TOTAL_CLOSE_

TIME. To reset the count, write 0.

81

2081 TOTAL_CLOSE_

TIME

0 hour

Total time where valve position is equal to or less

than OPEN_CLOSE_THRESHOLD. To reset the

count, write 0.

82

2082 OPEN_CLOSE_

THRESHOLD

0.25%

Threshold value for TOTAL_OPEN_TIME and

TOTAL_CLOSE_TIME.

83

2083 OPEN_TIME_LIM

2^32-1 hours

High-limit alarm setting for TOTAL_OPEN_TIME.

When TOTAL_OPEN_TIME has reached this

setting, a block alarm is generated.

84

2084 CLOSE_TIME_LIM

2^32-1 hours

High-limit alarm setting for TOTAL_CLOSE_TIME.

When TOTAL_CLOSE_TIME has reached this

setting, a block alarm is generated.