<19. Diagnostics>

19-4

IM 21B04C01-01E

(5) Positioner Signature
The positioner signature is the setpoint (input)-to-

position characteristics of the positioner, measured

at points in equal intervals within a specified range

over a round trip. The positioner signature reflects

the positioner Cv characteristics, cutoff level, and

limits, thus allowing the positioner setting conditions

to be ascertained.

• The following can be set in a setting parameter

POSITIONER_SIGN_SET:

Lower Setpoint [%]

Upper Setpoint [%]

Intervals [points]

Recommended Wait Time [seconds]

(read-only)

Wait Time [seconds]

• Performing measurement sets the setpoint in

SIGN_DATA_X and the position data (%) in

SIGN_DATA_Y.

• For the intervals, set the number of points of

measurement in the increasing direction within

the range of 4 through 20. The total number of

points of measurement in a round trip results in:

Intervals × 2 + 1.

For the wait time, set the retention time at each

point of measurement. For example, provided

the lower setpoint is set to 0, the upper setpoint

to 100, and the intervals to 10, the points of

measurement are 0, 10, 20, …90, 100, 90, 80,

…10, and 0, totaling 21 points.

*1: Applicable for Single Acting type with Code /BP.

19.3.3 Signature Measuring Result

The signature measuring result will be displayed to SIGN_MEAS_RESULT. While signature measuring is

running, “In operation” is displayed.

Table 19.1

Signature Measuring Result

Code

Message

Description

1

Succeeded

Signature measuring has succeeded.

2

Canceled

Signature measuring has been canceled.

10

Measure Actuator warning

While Standard Actuator Signature is running or preprocessing of

other Signature, warning has occurred.

20

Measure Extended Actuator warning

While Extended / High Resolution Actuator Signature is running,

warning has occurred.

30

Measure Step Response Test warning While Step Response Test is running, warning has occurred.

40

Measure Positioner warning

While Positioner Signature is running, warning has occurred.

100

Measure Actuator error

During Signature preprocessing, error has occurred.

255

In operation

Signature measuring is being executed.