A-15 – Yokogawa YVP110 User Manual

Page 126

Advertising
background image

<Appendix 1. Function Block Parameters>

A-15

IM 21B04C01-01E

Relative

Index Index

Parameter

Name

Valid Range

Default

(factory

setting)

Write

Description

22

17022 OP_

SELECT

0-8

0

A parameter to forcibly employ the input of a selected

number (Operator-settable)

23

17023 UPDATE_

EVT

Indicates event information if an update event (setting

change) occurs.

24

17024 BLOCK_

ALM

Indicates alarm information if a block alarm occurs.

25

17025 IN_5

0

Input 5

26

17026 IN_6

0

Input 6

27

17027 IN_7

0

Input 7

28

17028 IN_8

0

Input 8

29

17029 DISABLE_5 0, 1

0

Selector switch to disable input 5 from being selected

30

17030 DISABLE_6 0, 1

0

Selector switch to disable input 6 from being selected

31

17031 DISABLE_7 0, 1

0

Selector switch to disable input 7 from being selected

32

17032 DISABLE_8 0, 1

0

Selector switch to disable input 8 from being selected