<4. Wiring and Piping>

4-2

IM 21B04C01-01E

F0401.ai

Air supply port (SUP)

Output pressure port

(OUT1)

Output pressure port (OUT2)*

*Applicable only for Double

Acting Type

OUT2

Figure 4.1

Pneumatic Piping Ports

CAUTION

• To obtain the maximum air processing flow

rate of the YVP110, the inner diameter of

the piping tube needs to be at least 6 mm.

When the YVP110 is combined with a high-

capacity actuator and a minimum response

speed is required, use a tube whose inner

diameter is 6 mm or larger.

• Do not use an unnecessarily long tube or

piping as it will decrease the air flow rate,

thus leading to a decrease in response

speed.

• Perform sufficient flushing of the piping

tubes and fittings before use to ensure that

no foreign matter such as metal refuse may

enter the piping.

• When performing the piping connection, be

sufficiently careful that a piece of sealing

tape or other solid or fluid sealing material

does not enter the piping.

• When using the Double Acting Type and

piping to the OUT2 port, ensure that the plug

for the OUT2 Pressure Gauge does not get

turned around.

• When using the Double Acting Type, adjust

the pressure balance of the control relay as

required (in reference to Section 6.3.4).

4.3 Wiring

CAUTION

For flameproof equipment, wiring materials

and wiring work for these equipment including

peripherals are strictly restricted. Users

absolutely must read “Installation and Operating

Precautions for JIS Flameproof Equipment” at

the end of this manual prior to the work.

4.3.1 Recommended Cables

For wiring for a YVP110, use a cable for H1 fieldbus

segments specified by the Fieldbus F

OUNDATION

TM

.

A shielded cable is recommended. For the details

of cables required for H1 fieldbus segments, see

"Fieldbus Technical Information"(TI 38K3A01-01).
Choose cables suitable for the respective ambient

temperature ranges, especially when they are to be

laid in a hot or cold place.
When laying cables in or through a place where

the atmosphere may include a toxic gas or liquid,

or oil or solvent, choose wires and cables made of

materials that have sufficient durability.

4.3.2 Precautions on Wiring

IMPORTANT

• Prevent the cables from being affected

by noise induced from a high-capacity

transformer or power supply to a motor.

• As shown in Figure 4.2, remove the terminal

box cover and dust proofing plug when

performing a wiring connection. Be sure to

securely seal the unused wiring port with a

blind plug.

• To make the cables watertight and to

prevent them from being damaged, it is

recommended to use a cable conduit and

duct. Also for the same reasons, be sure to

use a watertight adapter for the connection

of the conduit to the port.