<14. DI Function Block>

14-2

IM 21B04C01-01E

14.5 Output

The value of the output OUT_D is generated based

on the value of PV_D.

14.6 IO_OPTS and STATUS_

OPTS

IO_OPTS and STATUS_OPTS are parameters that

stipulate options about block’s signal processing

and mode transitions. The settings of these options

are made by setting or resetting the respective bits:

on = true, off = false. Table 14.2 shows the options

available in IO_OPTS of a DI block.

Table 14.2

IO_OPTS of DI Block

Bit Position

Meaning

Description

0

Invert

Inverts the on/off status.

The table below shows the options available in

STATUS_OPTS of the AO block.

Table 14.3

STATUS_OPTS of DI Block

Bit

Position

Meaning

Description

3

Propagate

Fault Forward

Stipulates the handling of

the value and data status

of OUT_D when the quality

component of the data

status of SIMULATE_D falls

to Bad and the sub-status

component falls to device

failure or sensor failure.
If this option is true, then it:

- Does not generate a block

alarm.

- Sets the status and

value of SIMULATE_D in

OUT_D.

If this option is false, then it:

- Generates the “input

failure” block alarm.

- Set the quality and sub-

status components of

the status of OUT_D to

Bad and non specific,

respectively.

8

Uncertain if

Man mode

Sets the status of OUT_D

to uncertain when in Man

mode.

14.7 Alarm Processing

14.7.1 Block Alarms

When a condition shown in the table below is met

in a DI block, the DI block changes the bit statuses

of BLOCK_ERROR accordingly and generates a

block alarm.

Table 14.4

BLOCK_ERROR in AO Block

Bit Name of Error

Represented

Condition

3 Simulate Active SIMULATE_D is active.
7 Input Failure /

process variable

has BAD status

Propagate Fault Backward in

STATUS_OPTS is false, and

the sub-status component of

the status of READBACK is

sensor failure or device failure.

15 Out of Service

The target mode is O/S.

14.7.2 Discrete Alarm

The parameter DISC_ALM is a discrete alarm of the

parameter OUT_D.
When the value of OUT_D agrees with the value of

DISC_LIM, the alarm state of DISC_ALM is set to

active and an alert is generated.