<17. IS Function Block>

17-3

IM 21B04C01-01E

17.2 Input Section

17.2.1 Mode Handling

The Input Selector block’s operations are determined by the mode (parameter name: MODE_BLK). The

following describes operations in each mode.

Supported

Mode

Role

O/S

(Out of Service)

• System-stopped status

• Allows you to make changes to

configuration.

Man

• If you do not want to output the

value and status from IN or if the

value or status thus output is not

preferable, you can manually

transmit the value to OUT.

Auto

• Automatic system operation status

17.2.2 MIN_GOOD Handling

If there is no selectable input or if the number of selectable inputs is less than the value of MIN_GOOD,

SELECTED becomes “0.”

A case where the number of valid INs is less than the value of MIN_GOOD:

F1702.ai

OUT = certain retained

value that was

output previously

IN_1 = 23

SELECT_TYPE = Middle

STATUS_OPTS

MIN_GOOD = 3

SELECTION

SELECTED = 0

IN_2 = 34.5

IN_3 = 45

IN_4 = 2.34

IN_5 = 23.6

IN_6 = 15.5

IN_7 = 32.5

IN_8 = 27.4

DISABLE_1 = ON

DISABLE_2 = ON

DISABLE_3 = OFF

DISABLE_4 = ON

DISABLE_5 = OFF

DISABLE_6 = ON

DISABLE_7 = ON

DISABLE_8 = ON

OP_SELECT = 1

Figure 17.2 Example (1)

This example restricts the valid inputs using DISABLE_n, and the inputs are enabled only at DISABLE_3 and

DISABLE_5. Because the effective number of MIN_Good is 3, the input specified by OP_SELECT will not be

output.